Smith Cast Iron Boilers GB200 SERIES Скачать руководство пользователя страница 11

SECTION 3: START-UP & OPERATION

SEQUENCE OF OPERATION
For sequence of operation of the particular boiler being
installed, refer to Figures 2.8, 2.9, 2.10 and 2.11 in Section 2
of this manual.

Spill and rollout switches are mounted on all GB200 boilers. 

The spill switch detects the escape of combustion products
through the draft diverter relief opening and interrupts the
power to the gas valve preventing unsafe boiler operation.
Escape of flue products could be caused by a blocked or col-
lapsed chimney or inadequate chimney draft. This is a manu-
al reset-type device and can be reactivated by depressing
the spill switch reset button mounted on the left of the boiler’s
draft diverter (see Figure 2.1 for switch location).

The rollout switch prevents flame rollout from the boiler com-
bustion chamber, caused by blocked boiler flue passage-
ways, by interrupting power to the gas valve to prevent
unsafe boiler operation. This is a manual reset-type device
and can be reactivated by depressing the rollout switch reset
button mounted on the lower front jacket panel (see Figure
2.1 for switch location). Flue passages must be inspected by
a qualified installer if this problem occurs, prior to switch
replacement.

PRIOR TO START-UP
Fill system with water until the water level indicator (sight
glass) is approximately 2/3 full. This water level is 23" from
the surface on which the boiler sits.

SYSTEM START-UP & ADJUSTMENTS
Safe lighting and other performance criteria were met with
the gas manifold and control assembly provided on the boiler
when the boiler underwent tests specified in ANSI Z21.13-
LATEST EDITION

1.  Check combination gas valve on boiler and make sure it

is in the OFF position.

2.  For vent damper-equipped models, with the thermostat

set to call for heat, observe that vent damper position
indicator rotates to the open position (see Figure 2.5).
Damper must be in the open position when appliance
main burner is operating.

a. After damper opens, spark should appear at the pilot
ignition electrodes.

b. Set thermostat to no longer call for heat. Spark should
stop. Observe that damper position indicator rotates to
the closed position.

c. Set thermostat to call for heat.

3.  Light the boiler. For Model GB200 boilers with intermit-

tent pilot, see lighting instruction on Page 14.

4.  Observe pilot and main burner flame (see Figure 3.2).

All burner ports should be ignited and burn with a steady
blue flame.

CAUTION: Never leave the job with yellow burning
flames. This condition indicated poor combustion and
will quickly carbonize the boiler, reducing efficiency and
boiler life.  It may also be an indication of improper vent-
ing or combustion air supply.  If unable to adjust flame
properly, consult your local utility.

5.  Boilers are shipped from the factory with the primary air

shutters on the main burner wide open. It is recommend-
ed these air shutters be left in the wide open position
unless there is lifting of  the flame above the burner ports.
If there is lifting, the air shutters should be gradually
closed until the lifting is eliminated. It may also be neces-
sary to adjust the primary air shutters if the input rate is
reduced by a change in the orifices.

6.  After burner has been in operation for about 10 minutes,

check gas input rate to boiler as follows:

a. Make sure all appliances served by the meter are
turned off during timing of gas input rate to the boiler.

b. Measure the time in seconds that it takes for the boiler
to use 10 cubic feet of gas. Divide 36,000 by the number
of seconds (this is the number of cubic feet of gas used
per hour). Multiply this figure by the heating value of the
gas to obtain Btu input per hour. 

FIGURE 3.1: STEAM CONTROL ARRANGEMENT

WARNING: If boiler cannot be restored to normal
operation after re-setting of spill switch, or if flame
rollout switch has tripped, do not attempt to put the
boiler in operation. Immediately contact a qualified
service professional.

WARNING: Keep boiler area clear and free from com-
bustible materials, gasoline and other flammable
vapors and liquids.  Otherwise fire or explosion may
result.

PRESSURE
RELIEF VALVE

OPTIONAL
FLOAT
LOW WATER
CUT OFF

PRESSURE
CONTROL

PRESSURE
GAUGE

GAS VALVE

PRESSURE RELIEF
VALVE DISCHARGE
PIPING

11

Содержание GB200 SERIES

Страница 1: ...Step 1 Locating Setting Boiler 4 Step 2 Installing Steam Piping 5 Step 3 Installing Hydronic Components 5 Step 4 Venting Boiler 6 Step 5 Installing Testing Gas Piping 7 Step 6 Wiring Boiler 9 SECTION...

Страница 2: ...ting sys tem common venting system is likely to be too large for proper venting of appliances remaining connected to it At time of removal of existing boiler the following steps shall be followed with...

Страница 3: ...outside or through a vertical duct each opening must have a minimum free area of one square inch per 4000 Btu hr of gas input Horizontal ducts to the outside must have a minimum free area of one squar...

Страница 4: ...ting flue pipe between draft hood and chimney is as short as possible Observe the following minimum clearances to combustibles 18 on sides alcove at front 28 at top 18 at rear 6 from flue pipe in any...

Страница 5: ...r Check local code requirements if in doubt Discharge piping must be of same size or larger than the relief valve outlet and should be run as short and straight as possible Elbows in the discharge pip...

Страница 6: ...t be maintained The vent damper must be accessible for servicing and checking position indicator If applicable remove hairpin shipping clip which holds damper blade in closed position and observe that...

Страница 7: ...cautions STEP 5 INSTALLING TESTING GAS PIPING Connect the gas piping from the meter to the boiler using a pipe size which will result in a pressure drop of less than 0 3 W C for natural gas or 0 5 W C...

Страница 8: ...6 724 1086 2047 90 83 173 322 677 1023 1921 100 78 162 307 630 967 1811 125 69 146 275 567 866 1606 150 63 132 252 511 787 1498 1 2 3 4 1 1 1 4 1 1 2 2 8 FIGURE 2 7 GAS PIPE SIZING TABLES EXAMPLE Exam...

Страница 9: ...105 C rating Other wise insulation may melt or degrade exposing bare wire NOTE Boiler transformer must not be used to power external accessories i e zone valves relays etc Oth erwise transformer will...

Страница 10: ...tion Sequence for Boilers Equipped with Intermittent Pilot Vent Damper and 400 Series or M M PS804 LWCO FIGURE 2 11 Wiring Diagram Operation Sequence for Boilers Equipped with Standing Pilot Vent Damp...

Страница 11: ...trodes b Set thermostat to no longer call for heat Spark should stop Observe that damper position indicator rotates to the closed position c Set thermostat to call for heat 3 Light the boiler For Mode...

Страница 12: ...es be changed When changing orifices follow the procedures detailed in Section 4 of this manual 9 Start and stop burners several times by raising and low ering the thermostat setting 10 After boiler h...

Страница 13: ...setting 3 Turn off all electric power to the appliance 4 Remove control access panel if applicable 5 Rotate gas control knob clockwise to OFF 6 Wait five 5 minutes to clear out any gas Then smell for...

Страница 14: ...for clean ing Minerals in the water can build up on the heat trans fer surfaces and cause overheating and subsequent fail ure of the cast iron sections NOTE To reduce the risk of fouling the low wate...

Страница 15: ...off position While boiler is still hot drain completely through boiler drain Make sure that all low points in the return line are also completely drained These areas could trap chemicals and dirt 9 C...

Страница 16: ...e 59185 2 3 3 4 21 Low Water Cut Off CG400 50090 1 1 1 1 22 Pigtail 1 4 CG400 61684 1 1 1 1 23 Pressuretrol PA404A 50493 1 17 1 1 24 Press Gauge 0 15 P S I 60268 1 1 1 1 25 Water Gauge 59199 1 1 1 1 2...

Страница 17: ...5 24 V 43VA 50172 1 1 1 1 Honeywell Intermittent Pilot System 5 Pilot Ass y NG Q3451B 72352 1 1 1 Pilot Ass y NG Q3451B 72353 1 Pilot Ass y LP Q3451B 72358 1 1 1 Pilot Ass y LP Q3451B 72359 1 Ignition...

Страница 18: ...18 27 13 12 11 16 17 26 8 5 3 10 4 6 30 14 9 2 15 32 33 20 25 22 23 24 21 FIGURE 1 GB200 GENERAL ASSEMBLY 1 28 31 30 34...

Страница 19: ...19...

Страница 20: ...e living space Flames coming out around the appliance Yellow colored flames in the appliance Stale or smelly air The presence of soot or carbon in or around the appliance Very high unexplained humidit...

Отзывы: