BACnet Router Start-up Guide
Page 11 of 27
3.3.3 Power Jumper Settings
The FieldServer Carrier Board power jumper is set to position A by default but can be changed to position
B for other power supply requirements.
Position A:
The Carrier makes use of a full-wave rectifying bridge. Can be used for 12-24VAC input or
9
– 30VDC input. At 9VDC this becomes marginal.
Position B:
The Carrier makes use of a half-wave rectifying bridge. Best position for grounded AC
transformers and for using DC voltage down to 9VDC.
Power Jumper Switch
in position “A”
Figure 6: Power Jumper Switch