Sentry Instruction Manual - Version 6 

 

CONFIGURATION PROCEDURE 

Page:  37 

4.5  SENTRY MENU 

Table  4-2 describes the primary activities that can be accessed 
via the Sentry keyboard.  Each activity which involves sub-
menu selection is identified by an asterisk  Menu selections 
which refer to printer are standard in eight channel systems, 
optional in  two and four channel systems.  The MODBUS 
option replaces Printer software. 

Menu selections are further described in the following 
paragraphs.  Press the respective key to select the sub-routines 
and press the 

ENTER

 key to access them. Follow the sequence 

in the flow charts.  

MENU KEYS 

TEST 

RESET 

TIME 

MODE 

SYSTEM 

ALARMS 

HISTORY 

CALIBRATE/ 
CHANGE 

ALARMS 

SYSTEM 

PRINT HISTORY 

SELECT SCAN 

 

HISTORY 

PRINT SYSTEM 
REPORT 

CHECK CALIB 

 

 

PRINT STATUS 
REPORT 

CHECK MODULE 

 

 

SET DATE & 
TIME 

CHECK PRINTER 

Table 4-2 

Sentry Primary Menu Selection

 

4.5.1  TEST KEY 

The 

TEST KEY

 activities are described in the training exercise 

in Section 4.4. 

4.5.2  TIME KEY 

4.5.2.1  CHECK HISTORY 

PRESS ENTER TO 
CHECK HISTORY 

The first display in the 

CHECK HISTORY

 menu shows the 

system clock date and time 

D/T

 on the first line.  The second 

line shows the date and time at which the history information 
was last cleared 

HR.

 

The second display indicates the last time the power was 
interrupted. 

PD

 is the Power Down time and 

PU

 is the Power 

Up time. After any interruption of power to the controller the 

POWER

 light will flash until the system is reset. 

The third display begins the sequence in which the history  for 
any module can be recalled. The display will indicate 

MODULE

 

NUMBER

 

1.

  Successive presses of the 

ENTER

 

key will result in display of: 

− 

Date and time of the last low alarm 

LA

 and high alarm 

HA

 

− 

Highest concentration 

HC

 with date and time 

− 

Lowest concentration 

LC

 with date and time 

− 

Last Calibration with date and time. 

− 

Last logged error with date and time (if applicable). 

At the end of the sequence the display will indicate the next 
module number and will continue to automatically increment as 
the data is recalled. If the data from a particular module is not 
required press the 

UP

 arrow to manually increment the number.  

As this recall sequence is a continuous "loop", press the 

RESET

 

key at any time to return to the 

OPERATE

 

MODE

.   

The history information may be collected on a continuous basis 
without clearing the data because only the  last  occurrence of 
each level will be retained.  History data can be cleared by using 
the 

RESET

 

HISTORY

 menu selection.  Error messages are 

cleared by using the 

RESET

 

SYSTEM

 menu selection. 

4.5.2.2  PRINT HISTORY 

PRESS ENTER TO 

PRINT HISTORY 

When the printer option is installed in Sentry this menu choice 
can be used to print all the module history.   

4.5.2.3  PRINT SYSTEM 

PRESS ENTER TO 

PRINT SYSTEM 

When the printer option is installed in Sentry this menu choice 
can be used to print a complete system configuration report.

 

4.5.2.4  PRINT STATUS 

PRESS ENTER TO  

PRINT STATUS 

When the printer option is installed in Sentry this menu choice 
can be used to print a status report which indicates the present 
status and concentration for each module. 

Содержание 5000 Sentry

Страница 1: ...MODEL 5000 S E N T R Y GAS MONITORING SYSTEM Version 6 APPLICABILITY EFFECTIVITY Effective for all Sentry systems manufactured after September 1 1995 Instruction Manual Part Number T12001 A1...

Страница 2: ...stible Gas Cylinder Model 5358 00 Calibration Head Magnetic Model 5358 01 Calibration Head Standard Model 5360 00 Calibration Gas Delivery Fitting Notes 1 FMRC Approval applies only to conventional on...

Страница 3: ...N 19 3 5 1 CONTROLLER CONFIGURATIONS 19 3 5 2 CONTROLLER MOUNTING 19 3 5 3 ALARM DEVICE INSTALLATION 20 3 5 4 RELAY OUTPUTS 20 3 5 5 DC POWER LOAD 20 3 5 6 POWER UP 21 3 5 7 POWER DOWN 21 4 CONFIGURAT...

Страница 4: ...ALYSIS 66 7 4 3 ADJUSTMENT PROCEDURE 66 7 4 4 SENSOR REPLACEMENT 67 7 5 COMBUSTIBLE GAS SENSOR MODULE 5100 02 69 7 5 1 DESCRIPTION 69 7 5 2 TROUBLE ANALYSIS 69 7 5 3 ADJUSTMENT PROCEDURE 69 7 5 4 SENS...

Страница 5: ...PORTS 97 8 6 APPENDIX F MODEL 5392 INDIVIDUAL RELAY 99 8 6 1 RELAY PANEL DESCRIPTION 99 8 6 2 RELAY PANEL ASSEMBLY 99 8 6 3 INSTALLATION 99 8 6 4 OPERATION 99 8 6 5 INDIVIDUAL RELAY SPECIFICATIONS 99...

Страница 6: ......

Страница 7: ...the time of purchase or subsequent upgrade The enhancements which are described in detail in the appropriate sections of this manual include Addition of printer output firmware for models 5000 04 or 5...

Страница 8: ...sed to pass direct current DC from the controller to the modules The third wire transfers a series of very rapid pulses between the controller and the sensor modules This digital transfer of informati...

Страница 9: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 PRODUCT DESCRIPTION Page 3 Figure 1 1 Front Panel Display...

Страница 10: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 PRODUCT DESCRIPTION Page 4 Figure 1 2 Rack Mount Configuration Outline...

Страница 11: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 PRODUCT DESCRIPTION Page 5 Figure 1 3 NEMA 4 Configuration Outline...

Страница 12: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 PRODUCT DESCRIPTION Page 6 Figure 1 4 NEMA 7 Configuration Outline...

Страница 13: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 PRODUCT DESCRIPTION Page 7 Figure 1 5 Panel Mount Configuration Outline...

Страница 14: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 PRODUCT DESCRIPTION Page 8 Figure 1 6 Wall Mount Configuration Outline...

Страница 15: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 PRODUCT DESCRIPTION Page 9 Figure 1 7 Hydrogen Sulfide Module Outline...

Страница 16: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 PRODUCT DESCRIPTION Page 10 Figure 1 8 Combustible Sensor Outline...

Страница 17: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 PRODUCT DESCRIPTION Page 11 Figure 1 9 Oxygen and Toxic Sensor Modules Outline...

Страница 18: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 PRODUCT DESCRIPTION Page 12 Figure 1 10 Model 5100 05 Hydrogen Sulfide Sensor Module FMRC Approved Outline...

Страница 19: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 PRODUCT DESCRIPTION Page 13 Figure 1 11 Model 5100 25 Ammonia Sensor Module Outline...

Страница 20: ......

Страница 21: ...rdance with the National Electrical Code 2 4 SENSOR MODULES GENERAL Avoid installing sensor modules where they will be unnecessarily exposed to wind dust water esp direct hose down shock or vibration...

Страница 22: ......

Страница 23: ...thylene Oxide 1 52 Hydrogen 0 07 Hydrogen Chloride 1 27 Hydrogen Cyanide 0 94 Hydrogen Sulfide 1 19 Methane 0 55 Nitrogen Dioxide 1 58 Oxygen Air 1 10 Sulfur Dioxide 2 26 Table 3 1 Specific Gravity of...

Страница 24: ...bottom electronics board 2 Install the module housing onto the end of the supply conduit and or bolt into position as required Note If housing grounding is required for the installation a grounding lu...

Страница 25: ...oviding rear access for the module and alarm wiring 3 5 2 3 WALL MOUNTED CONTROLLER The wall mounted controller is provided on a sheet metal panel containing brackets which allow for removal of the co...

Страница 26: ...ccording to the manufacturer s instructions for the particular device Sentry dry contact relays provide switching capability as rated in the specifications See Appendix A NOTE Certain warning strobes...

Страница 27: ...TOR MISSING or UNCALIBRATED messages If the display indicates module numbers which match the numbers used in installation the wiring is correct and module configuration can begin If any number is omit...

Страница 28: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 Page 22 Figure 3 2 Controller Mounting Options...

Страница 29: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 Page 23 Figure 3 3 Sensor Module Mounting...

Страница 30: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 Page 24 Figure 3 4 Wiring Options...

Страница 31: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 Page 25 Figure 3 5 Typical Splice Box Wiring...

Страница 32: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 Page 26 Figure 3 6 Sensor Module Cross Section...

Страница 33: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 Page 27 Figure 3 7 Sensor Module Connector Detail...

Страница 34: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 Page 28 Figure 3 8 Sensor Module Top Plate Detail Typical...

Страница 35: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 Page 29 Figure 3 9 Controller Connector Panel Rack Configuration...

Страница 36: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 Page 30 Figure 3 10 Controller Connector Panel NEMA 4X Configuration...

Страница 37: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 Page 31 Figure 3 11 Typical Alarm Wiring Configuration...

Страница 38: ......

Страница 39: ...anged via the CHANGE mode Positive response messages such as SYSTEM RESET COMPLETE are displayed for 1 5 seconds to confirm that the activity has been completed Activity names are displayed bracketed...

Страница 40: ...xygen 16 5 Toxic 20 PPM Note Combustible Alarms cannot be set greater than 60 LEL 7 Latch L H Determine if any module will require a latching alarm and write Y in the appropriate position e g N Y indi...

Страница 41: ...ARROWS ENTER MODULE 1 9 ENTER GAS TYPE GGGG 10 ENTER 1 GGGG IS ON 11 ENTER LO ALM NONLATCH Use arrows to change 12 ENTER HI ALM LATCH Use arrows to change 13 ENTER HIGH ALARM XX Use arrows to change e...

Страница 42: ...ENTER Other user selectable display modes are described later in this manual Press the TEST button read the display then press the TEST button again Repeat until the system returns to the continuous s...

Страница 43: ...il the system is reset The third display begins the sequence in which the history for any module can be recalled The display will indicate MODULE NUMBER 1 Successive presses of the ENTER key will resu...

Страница 44: ...ting new history information When a user code has been installed the code will be required before the history can be reset 4 5 3 4 OTHER USE OF RESET KEY During CHANGE activity if the RESET key is pre...

Страница 45: ...he correct character is selected then ENTER to advance to the next character The module tag allows sixteen characters It is recommended that shorter tags be centered by leaving leading blank 4 6 1 4 O...

Страница 46: ...between calibrations and the status of global calibrate 4 6 2 3 CHECK MODULE PRESS ENTER TO CHECK MODULE Any module number can be selected and configuration information for that module recalled Select...

Страница 47: ...s E CHANGE MODULE Test Alarms Ts Ts E Module E MODE KEY PASSIVE Gas Type E Change Calib M E Module On Off E Select Scan M M E Low Alarm Latch Non E Check Calib M M M E High Alarm Latch Non E Check Mod...

Страница 48: ...EDURE Page 42 OPERATE MODE RESET RESET ALARMS RESET RESET HISTORY OPERATE MODE RESET SYSTEM RESET ALARMS ENTER SYSTEM RESET OPERATE MODE ENTER RESET ENTER CODE VALID RESET RESET HISTORY ACCESS DENIED...

Страница 49: ...E TEST TEST SYSTEM TEST FUNCTIONS TEST ALARMS TEST SYSTEM ENTER ENTER TEST CODE VALID ACCESS DENIED FULL DISPLAY TEST RETURN TO OPERATE MODE Y Y N ACTIVE HIGH ALARM ACTIVE TROUBLE ACTIVE LOW ALARM PAS...

Страница 50: ...DE LOWEST CONC VALUE D T LOW ALARM D T HIGH ALARM D T CHANGE MODULE NO POWER DOWN POWER UP REPORT REPORT COMPLETE SYSTEM REPORT ENTER REPORT REPORT COMPLETE TIME STATUS REPORT ENTER REPORT REPORT COMP...

Страница 51: ...ENTERS CHANGE MENU MODE KEY ACTIVE CONTINUOUS SAFE SCAN HIGHEST SENSOR CHECK CALIB ENTER MODE CHECK MODULE ENTER MODE CHECK PRINTER MODE ENTER CODE VALID ACCESS DENIED ENTER ENTER ENTER ENTER Y N GAS...

Страница 52: ...RATE ENTER MODE MODE SET USER CODE MODE ENTER CODE VALID ACCESS DENIED ENTER Y READ INSTRUCTIONS N N CHANGE MODULE MODE MODE MODE CHANGE PRINT MODBUS CHANGE GAS TAG CHANGE MOD TAG MODE ENTER ENTER ENT...

Страница 53: ...tic switch in one of the sensors is not functioning 5 1 2 LOCAL CALIBRATION When Global Calibration is turned off the Sentry controller collects zero and span value data from each sensor module eligib...

Страница 54: ...message is a notification only and does not cause the module to go out of service The message can be suppressed by setting the calibration frequency to 00 days at the time of calibration 6 Select Cali...

Страница 55: ...Use magnetic or non magnetic calibration gas delivery fitting During the time calibration gas is being delivered the upper display on the controller will continue to cycle through all applicable modul...

Страница 56: ...meation tube calibrator The controller will display the concentration which would be determined based on the prior calibration of the module 5 Remove the gas and the calibration head replace the rains...

Страница 57: ...7 ETO 1 000 cc min 3 minutes Table 5 1 Calibration Gas Flow Rates 5 3 3 1 HYDROGEN SULFIDE Hydrogen Sulfide gas must be supplied from a permeation tube device or from Sierra Monitor Model 9200 series...

Страница 58: ......

Страница 59: ...retention should be replaced every two years See Service 3 DUST AND DIRT CONTROL When calibration is performed the controller and the modules should be checked visually to determine if dust or dirt b...

Страница 60: ......

Страница 61: ...e Water accumulation in sensor module enclosures is a major cause of damage and system failures take precautions to seal electrical conduits and provide moisture traps and drains to avoid water damage...

Страница 62: ...Check module channel wiring Check connector panel seating to controller Check 20V between channel pins 1 and 3 Check 15 12V supply Check for oscillation on channel pin 2 Correct above items replace an...

Страница 63: ...onent failure wrong address reversed wiring Component failure controller RAM initialized incorrectly wire gauge too small Sensor Module electronics failure Signal voltage misadjusted environmental det...

Страница 64: ...ted side panel on the right side of the controller Field repairs to the main control board involve socketed component replacement only Board removal is not required for these repairs 7 2 1 4 FRONT PAN...

Страница 65: ...board Figure 7 2 The EPROM can be identified by the white label on the window The EPROM stores all the software for Sentry The EPROM needs replacement when the user wishes to upgrade to additional opt...

Страница 66: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 SERVICE Page 60 Figure 7 1 Controller Exploded View...

Страница 67: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 SERVICE Page 61 Figure 7 2 Control Board Component Locator...

Страница 68: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 SERVICE Page 62 Figure 7 3 Power Supply Component Locator...

Страница 69: ...ge Current Type 2 Module Sensor type Type 1 through 4 Modules Calibration switch condition on off Module voltage tests line drop from controller to module Reference voltage used together with ground t...

Страница 70: ...Reset History command All other modules on the channel and modules on other channels remain in full operation and continue to be scanned by the controller If the problem is corrected the trouble ligh...

Страница 71: ...a typical diagnostic report Report Description ID A Controller Identification 11 20 15 16 Time report was generated S1 0 376 Data that follows is for Module 1 Sensor Signal is 0 376 VDC BV 2 021 Brid...

Страница 72: ...e module off using the CHANGE MODULE mode Note Although all the necessary data can be collected with a voltmeter at the sensor module some helpful information can be displayed or printed See diagnosti...

Страница 73: ...10K ohms 2 Heater resistance red wires should be between 20 and 35 ohms 3 Calibration switch green wires should be open in normal operation and should close when the calibration magnet is applied If t...

Страница 74: ...45 4 05 3 85 4 38 2 66 3 43 3 06 3 73 3 46 4 06 3 86 4 39 2 67 3 43 3 07 3 73 3 47 4 07 3 87 4 40 2 68 3 44 3 08 3 74 3 48 4 07 3 88 4 41 2 69 3 45 3 09 3 75 3 49 4 08 3 89 4 41 2 70 3 46 3 10 3 76 3...

Страница 75: ...llected with a voltmeter at the sensor module some helpful information can be displayed or printed See diagnostic codes 0004 and 0008 in Appendix C 7 5 3 ADJUSTMENT PROCEDURE Prior to reading voltages...

Страница 76: ...does not adjust the electronics so that the gain is large enough to cause false alarms due to minor drift or due to minimal electronic noise 7 5 4 SENSOR REPLACEMENT If any of the above adjustments c...

Страница 77: ...93 Ethyl Alcohol 73 132 Ethylamine 53 95 Ethyl Benzene 36 65 Ethyl Bromide 91 165 Ethyl Chloride 57 103 Ethylcyclopentane 40 72 Ethylene 71 128 Ethylenedichloride 66 120 Ethyleneoxide 52 94 GAS METHA...

Страница 78: ...onics enclosure wiring damage or corrosion Use Figure 7 7 to locate test points during the following procedures 7 6 3 1 SIGNAL ADJUSTMENT It is unlikely that any electrical adjustment will be required...

Страница 79: ...rness to the transmitter electronics Replace the transmitter into the enclosure make signal adjustments as described above and replace the enclosure cover After the sensor is installed Update new sens...

Страница 80: ...module some helpful information can be displayed on the controller or printed See diagnostic codes 0004 and 0008 in Appendix C 7 7 3 ADJUSTMENT PROCEDURE Prior to reading voltages and making adjustme...

Страница 81: ...the housing and unplug the old sensor from the bottom board remove it from the enclosure hub and reverse the procedure to install the new sensor After the sensor is installed Allow one hour of stabili...

Страница 82: ...tmeter at the sensor module some helpful information can be displayed on the controller or printed See diagnostic codes 0004 and 0008 in Appendix C 7 8 3 ADJUSTMENT PROCEDURE Prior to reading voltages...

Страница 83: ...odule 7 8 3 3 SENSOR OUTPUT ADJUSTMENT The following procedure is to be used when during normal calibration of a new sensor the span voltage cannot be adjusted to a high enough level 1 Adjust the span...

Страница 84: ...s are received due to sensor inaccuracy Warning During sensor adjustments the concentration reading on the controller will be inaccurate and alarm level concentrations may be displayed If false activa...

Страница 85: ...cover on the sensor assembly including the spacer washer 8 Install the sensor assembly into the enclosure and tighten firmly 9 Reconnect the sensor harness to the transmitter install the transmitter i...

Страница 86: ...e 80 7 Apply span gas Adjust the gain potentiometer until TP10 correct value as described above To increase voltage at TP10 turn the gain potentiometer counter clockwise 8 Remove system power and re i...

Страница 87: ...off using the Change Module mode NOTE Although all the necessary data can be collected with a voltmeter at the sensor module some helpful information can be displayed on the controller or printed See...

Страница 88: ...electronics board To replace the sensor assembly 1 Confirm that system power has been removed 2 Remove the transmitter electronics board from the main housing and unplug the sensor harness from the tr...

Страница 89: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 APPENDIX A SPECIFICATIONS Page 83 8 APPENDICES...

Страница 90: ......

Страница 91: ...ne filter TRANSMISSION Digital pulse width modulated RFI EMI immune B PHYSICAL DIMENSIONS Controller Rack Mount 7 X 4 5 X 12 H W D 17 5cm X 11 25cm X 30cm NEMA 4X Enclosure 17 5 X 16 2 X 6 35 H W D 44...

Страница 92: ...ft Less than 1 per month Typical Life 2 years in normal service Warranty 1 year Chlorine 5100 06 Range Factory 10 PPM Max 100 PPM Operating Temperature 4o F to 122o F 20o C to 50o C Relative Humidity...

Страница 93: ...25 Range Factory 50 PPM Max 50 PPM Relative Humidity 20 90 RH Operating Temperature 14o F to 113o F 10o C to 45o C Response 30 seconds to 90 indication Calibration Frequency 90 Days Recommended Zero D...

Страница 94: ......

Страница 95: ...tion or application or on which original identification marks have been removed or altered This Limited Warranty also will not apply to interconnecting cables or wires consumables i e calibration gase...

Страница 96: ......

Страница 97: ...fourth digits in the same manner 5 When an entry code has been established that code must be used to access the controlled sections of the menu 6 User numbers 1 through 5 have access to all Sentry fun...

Страница 98: ...lete all codes as described above To enter the CALIB CHANGE activity 1 Turn Sentry off and then on to start the warm up 2 Press RESET key three times to RESET HISTORY 3 Press ENTER to display USE ARRO...

Страница 99: ...ate NEMA 4 Encl Printer Options 5301 51 Printer Package Single Controller Rack 5301 52 Printer Package 2 Controller Rack 5301 53 Printer Package 3 Controller Rack 5301 54 Printer Package 4 Controller...

Страница 100: ...nel 5100 99 Input Module Analog Digital 1 channel Sensor Module Accessories 5311 00 Rainshield 5394 00 Duct Mount Fitting 5398 01 Sample Draw Assembly 5398 02 Sample Draw Dilution Assembly 5398 24 Sam...

Страница 101: ...oxide CO2 9211 07 Permeation Tube Hydrogen Chloride HCI 9211 08 Permeation Tube Hydrogen Cyanide HCN 9211 09 Permeation Tube Ammonia NH3 9220 00 Calibrator Kit Toxic Gas w o cylinders 9221 01 Gas Cyli...

Страница 102: ......

Страница 103: ...by selecting SET USER CODE and answering with user number 9 and entry code number 0010 8 5 3 2 OPERATIONAL REPORTING CALIBRATION REPORT The calibration report prints automatically when a calibration h...

Страница 104: ...lso begin with the present system date and time All printer reports end with a line across the page This allows the user to confirm that the entire report has printed and helps with differentiation wh...

Страница 105: ...vidual Relay Panel ribbon cable into the connector on the controller 4 Mount the panel on the four stand offs on the connector panel of the controller not required for NEMA enclosures 5 Make the neces...

Страница 106: ...0 0 0 1 0 0 0 1 1 1 0 1 1 F F 1 0 0 0 1 1 1 0 0 0 1 0 0 0 0 1 0 0 0 1 1 1 0 1 1 F F 1 0 0 1 1 0 F F 1 1 0 0 1 1 0 F F 0 0 0 0 1 0 0 0 1 1 1 0 0 1 1 0 F F F 1 0 0 1 1 0 F F 1 1 0 0 1 1 0 F F 0 No Alarm...

Страница 107: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 APPENDIX F MODEL 5392 INDIVIDUAL RELAY Page 101 Figure 8 2 Individual Relay Panel...

Страница 108: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 APPENDIX F MODEL 5392 INDIVIDUAL RELAY Page 102 Figure 8 3 Individual Relay Panel Installed View...

Страница 109: ...sion Panel connector cable into the connector panel of the controller See J3 Figure 8 4 not required for NEMA enclosures 4 Connect the two position DC power connector to Power P and Ground G on any ch...

Страница 110: ...utputs can be forced to 4 mA by using diagnostic code 0012 The analog outputs can be forced to 20 mA by using diagnostic code 0013 The analog outputs can be returned to normal operation by using diagn...

Страница 111: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 APPENDIX G MODEL 4314 OUTPUT EXPANSION PANEL Page 105 Figure 8 4 Model 4314 01 Output Expansion Module...

Страница 112: ...1 VDC to the analog input device Connect signal S on TB2 to the corresponding terminal on the analog input device 8 8 3 ADJUSTMENT PROCEDURE Prior to reading voltages and making adjustments perform a...

Страница 113: ...or modules on the same controller must not have addresses which duplicate addresses used on the 5100 90 5 Set select switches on the right side of the converter to identify the sensor module type as f...

Страница 114: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 APPENDIX J REFERENCE DRAWINGS Page 108 Figure 8 6 Model 5100 90 Analog Input Multiplexor...

Страница 115: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 APPENDIX J REFERENCE DRAWINGS Page 109 8 10 APPENDIX J REFERENCE DRAWINGS...

Страница 116: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 APPENDIX J REFERENCE DRAWINGS Page 110 Figure 8 7 Typical Rack Configuration Wiring...

Страница 117: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 APPENDIX J REFERENCE DRAWINGS Page 111 Figure 8 8 Typical NEMA 4X Wiring...

Страница 118: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 APPENDIX J REFERENCE DRAWINGS Page 112 Figure 8 9 Rainshield and Calibration Adapter...

Страница 119: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 APPENDIX J REFERENCE DRAWINGS Page 113 Figure 8 10 Duct Mount Fitting Components...

Страница 120: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 APPENDIX J REFERENCE DRAWINGS Page 114 Figure 8 11 Duct Mount Fitting Assembled View...

Страница 121: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 APPENDIX J REFERENCE DRAWINGS Page 115 Figure 8 12 Instrument Rack Dimensions...

Страница 122: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 APPENDIX J REFERENCE DRAWINGS Page 116 Figure 8 13 Enclosure NEMA 4 NEMA 7 Groups B C D...

Страница 123: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 APPENDIX J REFERENCE DRAWINGS Page 117 Figure 8 14 Remote Sensor Connection Diagram...

Страница 124: ......

Страница 125: ...55 CHECK POWER ADJ 63 64 66 CHECK PRINTER 37 40 COMBUSTIBLE GAS 1 15 48 53 69 71 COMBUSTIBLE GAS MODULE 69 COMBUSTIBLE GAS SCALING FACTORS 71 CONNECTOR PANEL 58 CONTINUOUS 35 36 39 CONTINUOUS SCAN 35...

Страница 126: ...92 RESET KEY 38 RESET SYSTEM 35 37 38 S SAFE SCAN 39 SENSOR FAILURE 63 64 66 69 72 74 76 78 79 81 82 SET DATE TIME 38 SET USER CODE 35 38 41 91 92 97 SPECIFICATIONS 85 99 104 STATUS INDICATORS 1 STATU...

Страница 127: ...Test Key Flow Chart 43 Figure 4 5 Sentry Time Key Flow Chart 44 Figure 4 6 Sentry Mode Key Passive Flow Chart 45 Figure 4 7 Sentry Mode Key Active Flow Chart 46 Figure 5 1 Model 5358 00 Calibration A...

Страница 128: ...Table 3 6 Sentry Enclosure Options 19 Table 3 7 Sentry Power Load 20 Table 4 1 Display Conditions 36 Table 4 2 Sentry Primary Menu Selection 37 Table 5 1 Calibration Gas Flow Rates 51 Table 7 1 Sentry...

Страница 129: ...A BUG WHICH WILL CAUSE SHRINKING OF FIGURE CROSS REFERENCES USE ONLY WORD 6 0a UPDATED ON GORDON ARNOLD S COMPUTER 11 95 OR USE AN UPDATED 7 0 SYSTEM ALWAYS CHECK CONTENT INDEX AND LISTS FOR ACCURATE...

Страница 130: ...on 6 Sierra Monitor Corporation 1991 Tarob Court Milpitas CA 95035 408 262 6611 Applicability Effectivity APPLICABILITY EFFECTIVITY Effective for all Sentry systems manufactured after September 1 1995...

Отзывы: