SMC
sierra monitor corporation
Sentry Instruction Manual - Version 6
APPENDIX J - REFERENCE DRAWINGS
Page: 107
8.9 APPENDIX I - MODEL 5100-90 8-CHANNEL
ANALOG-DIGITAL CONVERTER
8.9.1 DESCRIPTION
The 8-Channel Analog-Digital Converter can be used to
connect up to eight 4-20 mA sensor devices from Sierra
Monitor or other manufacturers to the Sentry controller.
8.9.2 INSTALLATION
1. Power down the system
2. Figure 8-6 shows the terminal connections for the 8-
Channel Analog-Digital Converter.
3. Connect 4-20 mA sensor inputs for each of the
sensors (up to 8) to channels 1 through 8 as indicated
•
3-wire connections should be P (Power), S
(Signal), G (Ground)
•
2-wire connections should be P (Power) and S
(Signal)
4. The channel number indicated by the connection on
the 5100-90 becomes the Sentry module address
number
•
NOTE
: Sentry digital input sensor modules on the
same controller must not have addresses which
duplicate addresses used on the 5100-90
5. Set select switches on the right side of the converter
to identify the sensor module type as follows:
Type
Switch 1
Switch 2
Combustible
OFF
ON
Oxygen
ON
OFF
Toxic
OFF
OFF
Not Active
ON
ON
6. The Power/Comm Bus is located at the bottom of the
converter. Connect Power/Comm Bus to the Sentry or
an external 20-24 VDC Power Supply as follows:
Converter
Sentry
External 20-24VDC
Power Supply
P1
Terminal 1
Channel 8
Power Supply
+VDC
S1
Terminal 2
Channel 8
Terminal 2
Channel 8
G1
Terminal 3
Channel 8
Terminal 3
Channel 8K
P2
Terminal 1
Channel 7
Power Supply
+VDC
G2
Terminal 3
Channel 7
Power Supply
Common
•
NOTE
: Converter terminals P1, S1 and G1
connect to one channel and P2, G2 connect to a
second channel. When an external power supply
is used, connect S1 and G1 to any single channel
on the Sentry
8.9.3 SERVICE
There are no serviceable components on the Analog-
Digital Converter. Contact Sierra Monitor for factory
service.
Содержание 5000 Sentry
Страница 6: ......
Страница 20: ......
Страница 22: ......
Страница 29: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 Page 23 Figure 3 3 Sensor Module Mounting...
Страница 30: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 Page 24 Figure 3 4 Wiring Options...
Страница 31: ...SMC sierra monitor corporation Sentry Instruction Manual Version 6 Page 25 Figure 3 5 Typical Splice Box Wiring...
Страница 38: ......
Страница 58: ......
Страница 60: ......
Страница 90: ......
Страница 94: ......
Страница 96: ......
Страница 102: ......
Страница 124: ......