- 10 - 

No.VP500-OMZ0005 

Problem

 

When the valve is failing, use this flow chart 
to  clarify  the  cause  of  the  failure  and  take 
countermeasures appropriate for the cause.

 

Possible cause

 

Countermeasures

 

Response 

failure 

 

Valve and 

actuator 
become 

slow. 

 

1) Leakage current 

When the valve is turned off, it became slow 
due to the residual voltage.   

Check the residual voltage. 
Keep the residual voltage at 3% of the rated 
voltage (DC coil) or less. 

 

2) Clogging of the filter and silencer 

Filter  or  silencer  is  clogged,  or  vent  port  is 
blocked. 

- Replace the filter. 
- Replace the silencer. 
- Do not block the valve vent port.   

 

3) Operation failure or sticking of the main 
valve. 

Foreign matter from the piping and air source 
got  caught  in  the  main  valve  of  the  valve, 
causing a delay.   
Malfunction occurred due to sticking such as 
swelling of the rubber part of the main valve. 

- Replace the valve. 
- Check for abnormalities in devices other 

than valves. 

- Clean the air supply. 
- If incorrect oil has been used for lubrication, 

remove the oil by air blow. 

- If there is a large amount of condensate, 

install an auto drain or a dryer. 

Air leakage 

 
 
 
 

1) Internal air leakage increased because 
foreign  matter  get  caught  in  the  main 
valve. 

- Replace the valve. 
- Clean the air supply. 

2) Sealing failure of the actuator (cylinder) 

- Refer to the operation manual of the actuator 
for details. 

1)  Foreign matter is  caught  in  the  pilot 
valve armature. 

- Replace the valve. 
- Clean the air supply. 

 

2)

 

Foreign matter caught in the valve seat 

- Replace the valve. 
- Clean the air supply. 

If the countermeasures above are not effective, there may be a problem with the valve. 
Stop using the valve immediately. 
 
 
If any of the examples below are applicable, there may be an internal problem with the valve. Stop using the valve immediately. 
1. 

  The voltage used was not the rated voltage. 

2. 

  The oil supplied was not the specified type. 

3. 

  Lubrication was stopped during operation. Or, lubrication was interrupted temporarily. 

4. 

  The product was directly exposed to water with the valve cover, connector block or SI unit removed.   

5. 

  Severe impact was applied. 

6. 

  Foreign matter such as condensate or dust has entered the product 

7. 

  Other than those specified, if precautions on the operation manual apply. 

 

 If the product has failed, then please return the valve without any modifications. 

The valve is slow. 
Actuators including cylinder become slow.   

Find and check the air leakage point. 

1. Air leakage from OUT. 
[2(A)] port or EXH. [3(R)] port. 

2. Air  leakage  from  the  vent 
port. 

Содержание VP500 Series

Страница 1: ...Doc No VP500 OMZ0005 PRODUCT NAME 3 Port Solenoid Valve Modular Type Residual Pressure Release Valve MODEL Series VP 46E Series 5 7...

Страница 2: ...Contents Contents 1 Safety Instructions 2 3 Design Selection 4 5 Mounting 5 Piping 5 Wiring 5 Lubrication 5 Air Supply 5 6 Operating Environment 6 Maintenance 6 Specific Product Precautions 7 8 Troubl...

Страница 3: ...equipment failure when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly T...

Страница 4: ...of the product 3 Prior to using SMC products please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products 2 Vacuum pads are excluded from th...

Страница 5: ...hat the leakage voltage will increase when a resistor is used in parallel with a switching element or when a C R circuit surge voltage suppressor is used for protecting a switching device because of t...

Страница 6: ...ied voltage When electric power is connected to valve be careful to apply the proper voltage Improper voltage may cause malfunction or coil damage 3 Check the connections Check if the connections are...

Страница 7: ...tact with oil weld spatter etc exercise preventive measures 9 When the valve is mounted in a control panel make sure the ambient temperature is within the specifications of the valve 1 Temperature of...

Страница 8: ...side of the range of supported sizes 3 5 to 7 will not satisfy IP65 enclosure standards Also be sure to tighten the gland nut and holding screw within their specified torque ranges After separating th...

Страница 9: ...angerous situation due to air accumulated between the check valve and the pilot valve Soft start up function When the soft start up function is selected the initial pressure of the pneumatic system ca...

Страница 10: ...e oil does not splash from the exhaust port 3 R vent port 1 Non conforming of electric system Incorrect wiring Fuse blown out lead wire broken Incorrect contact at the contact and connection Sequencer...

Страница 11: ...reased because foreign matter get caught in the main valve Replace the valve Clean the air supply 2 Sealing failure of the actuator cylinder Refer to the operation manual of the actuator for details 1...

Страница 12: ...Chiyoda ku Tokyo 101 0021 JAPAN Tel 81 3 5207 8249 Fax 81 3 5298 5362 URL https www smcworld com Note Specifications are subject to change without prior notice and any obligation on the part of the m...

Отзывы: