-78-
No.PF
※※
-OMY0002
●
Device access lock parameter (index 12)
The contents are as follows.
Data type: 16 bit Record
Value
Contents
0
Key lock release, DS unlock (Initial value)
2
Key lock release, DS lock
8
Key lock, DS unlock
10
Key lock, DS lock
[Key lock]
This function prevents the user from physically changing the setting of the flow switch (button operation is
not accepted).
Even when key lock function is activated, settings can be changed by IO-Link communication.
Restoration by data storage (overwriting parameter data) can be performed.
[Lock data storage (DS lock)]
Locking "Data storage" will invalidate the data storage function of the flow switch.
In this case, access will be denied for backup and restoration of data storage.
●
Device state parameters (index 36)
Readable device states are as follows.
Data type: 8 bit UInteger
Value
State definition
Description
0
Normal operation
-
1
Maintenance inspection required
Not available
2
Outside specification range
Outside the flow measurement range
Below the flow measurement range
3
Function check
Not available
4
Failure
Internal failure of digital flow switch
●
Device detail status parameters (index 37)
Detailed event contents of readable device status are as follows.
Array
Event content
Event classification
Event code
Definition
Value
1
Internal failure of digital flow switch
Error
0xF4
0x8D03
2
Internal failure of digital flow switch
Error
0xF4
0x8D04
3
Internal failure of digital flow switch
Error
0xF4
0x8D05
4
Internal failure of digital flow switch
Error
0xF4
0x8D01
5
Internal failure of digital flow switch
Error
0xF4
0x8D06
6
Internal failure of digital flow switch
Error
0xF4
0x8D08
7
OUT2 over current error
Error
0xF4
0x8CC0
8
Outside the accumulated flow measurement
warning
0xE4
0x8D80
9
Outside the instantaneous flow measurement
warning
0xF4
0x8C10
10
Below the instantaneous flow measurement
warning
0xE4
0x8C30
11
Test event A
warning
0xE4
0x8CA0
12
Test event B
warning
0xE4
0x8CA1
13
Data storage upload request
notification
0x54