-29-
No.PF
※※
-OMY0002
Simple Setting Mode
<Operation>
[Simple setting mode (hysteresis mode)
In the simple setting mode, the set value and hysteresis can be changed while checking the current flow value
(main screen).
(1) Press and hold the SET button for 1 to 3 seconds in measurement mode. [SEt] is displayed on the main
screen. When the button is released while in the [SEt] display, the current flow value is displayed on the
main screen, [P_1] or [n_1] is displayed on the sub screen (left side), and the set value is displayed on the
sub screen (right side) (Flashing).
(2) Change the set value with the UP or DOWN button, and press the SET button to set the value. Then, the
setting moves to hysteresis setting. (The snap shot function can be used. (Refer to page
))
(3) Change the set value with the UP or DOWN button, and press the SET button to set the value. Then, the
setting moves to the setting of OUT2.
(The snap shot function can be used. (Refer to page
))
(4) Press the SET button for less than 2 seconds to complete the OUT1 setting.
[P_2] or [n_2] is displayed on the sub screen (left side). Continue with setting the OUT2.
Press and hold the SET
button for 2 seconds or longer to complete the setting. The product will return to
measurement mode.
1: Selected items (1) to (3) become valid after pressing the SET button.
2: After enabling the setting by pressing the SET button, it is possible to return to measurement mode by pressing the SET button
for 2 seconds or longer.
3: When the output mode (refer to page
) is set to error output or output OFF, the simple setting mode cannot be used.
(The setting changes to measurement mode by releasing the button when [SEt] is displayed.)