■[F 0] Selection of reference condition, unit selection function, switch output specifications.
Reference condition
Standard condition or normal condition can be selected.
Standard condition (ANR) and normal condition (NOR) are defined as follows:
Standard condition (ANR): 101.3 kPa, 20 °C
Normal condition (NOR): 101.3 kPa, 0 °C
Unit selection function
The selectable display units are L/min or CFM (ft
3
/min).
This setting is only available for models with the unit selection function.
: This function is not displayed for models without unit selection function.
<Operation>
Press the UP or DOWN button in function selection mode to display [F 0].
Press the SET button.
Move on to the reference condition setting.
Reference condition setting
Press the UP or DOWN button to select the reference condition.
Press the SET button to set.
Move on to display unit setting.
Display unit setting
Press the UP or DOWN button to select the display unit.
: A product with no units selection function (fixed to SI units) does not indicate the display unit [Ft].
Press the SET button to set.
Move on to the switch output NPN/PNP
specification switching setting.