-34-
No.PF
※※
-OMW0004-A
Troubleshooting
If an operation failure of the product occurs, please confirm the cause of the troubles from the following table.
If a cause applicable to the troubles cannot be identified and normal operation can be recovered by
replacement with a new product, this indicates that the product itself was faulty. Problems with the product
may be due to the operating environment (installation etc). Please consult SMC.
Cross-reference for troubleshooting
Fault
Detail
Possible cause
Item to check
Recommended action
Incorrect
display
(Integrated
display
type)
No display
Incorrect wiring
Check if the brown wire DC(+) and blue
wire DC(-) are connected correctly.
Correct the wiring.
Loose connector
Check that the connector is connected.
Connect the connector.
The display
is unstable.
Foreign matter
has entered or got
stuck inside the
flow passage of
the sensor.
Confirm whether foreign matter may
enter.
We recommend a filter with
filtration of approx. 40
mesh.
Piping is
connected in the
wrong direction.
Confirm whether the mounting direction
of the product corresponds to the flow
direction.
Make the mounting
direction correspond to the
flow direction.
Insufficient water
supply
Confirm whether the fluid path is full.
Fill up the fluid path.
Pulsation in the
flow.
Confirm whether the supply pressure
fluctuates, or whether pulsation is
generated due to the characteristics of
the compressor or pump used as the
pressure source.
Change to a pump that has
less pulsation. Install a tank
to reduce the pressure
fluctuation. Change the
piping to elastic piping such
as rubber hose.
Incorrect
display
Foreign matter
has entered or got
stuck inside the
flow passage of
the sensor.
(1) Confirm whether foreign matter may
enter.
(2) Confirm whether any foreign matter
has got stuck inside.
We recommend a filter with
filtration of approx. 40
mesh.
Remove foreign matter.
Piping is
connected in the
wrong direction.
Confirm whether the mounting direction
of the product corresponds to the flow
direction.
Make the mounting
direction correspond to the
flow direction.
Insufficient water
supply
Confirm whether the fluid path is full.
Fill up the fluid path.
Pulsation in the
flow.
Check if there is supply pressure
fluctuation or pressure pulsation due to
the characteristics of the compressor or
pump acting as the pressure source.
Change to a pump with
less pulsation.
Install a tank to reduce the
pressure fluctuation.
Change to elastic piping
such as rubber hoses.
Flow does
not start.
The flow
adjustment valve
is closed.
Check the condition of the flow
adjustment valve.
Open the flow adjustment
valve to get appropriate
flow.
Stop valve is
closed.
Check for the stop valve.
Open the stop valve.
Содержание PF3W504
Страница 12: ...11 No PF OMW0004 A Model Indication and How to Order Integrated type Basic type...
Страница 13: ...12 No PF OMW0004 A Integrated type Straight type...
Страница 14: ...13 No PF OMW0004 A Remote type Supply type...
Страница 15: ...14 No PF OMW0004 A Remote type Return type...
Страница 51: ...50 No PF OMW0004 A Characteristics graph Measurable range of ethylene glycol aqueous solution reference value...
Страница 55: ...54 No PF OMW0004 A Flow range 2 to 16 L min symbol 20 reference value Nil S P W...
Страница 56: ...55 No PF OMW0004 A Flow range 5 to 40 L min symbol 40 reference value Nil S P W...
Страница 58: ...57 No PF OMW0004 A Flow range 2 to 16 L min symbol 20 reference value Nil S P W...
Страница 59: ...58 No PF OMW0004 A Flow range 5 to 40 L min symbol 40 reference value Nil S P W...