-36-
No.PF
※※
-OMG0010-G
■
Error indication
Error Name
Error Display
Error Type
Troubleshooting Method
Excessive
instantaneous flow
Flow has exceeded the upper
limit of the display flow range.
Reduce the flow.
Over current error
The switch output load current
is more than 80 mA (OUT1).
Turn the power off and remove
the cause of the over current.
Then turn the power on again.
System error
The set data has been
changed unexpectedly.
To reset, press the
button for
6 seconds or longer while the
button is pressed. Then set all
data again.
The internal circuit could be
damaged.
Stop using and please contact
SMC.
Excessive
accumulated flow
(When [ U_1] is selected)
Exceeds the range of the 2nd
turn of flow indication.
To reset the accumulated flow
value, press the
button for
6 seconds or longer while the
button is pressed.
(When [ U_2] is selected)
Accumulated
flow displayed
(flashing)
: If the error cannot be reset after the above measures are taken, then please contact SMC.