[F_6] Input of the Set point
When Instantaneous output mode is selected
<Operation>
Press the
,
and
buttons in function selection mode to display [F_6].
Press the
button.
Input of the Set point 1
[ n_1]
and the current Set value are
displayed in turn.
Press the
and
button to change
the value referring to list of outputs (page
19
).
: When Non-Reverse output has been selected as the switch operation, [P_1] is displayed.
Press the
button.
Input of the Set point 2
[ n_2]
and the current Set value are
displayed in turn.
Press the
and
button to change
the value referring to list of outputs (page
19
).
: When Non-Reverse output has been selected as the switch operation, [P_1] is displayed.
Press the
button.
Input of hysteresis
This setting is available when Set point 1 < Set point 2.
It will not be displayed when Set point 1
≧
Set point 2.
[ HIS] and the current Set value are
displayed in turn.
Press the
and
button to change
the value referring to list of outputs (page
19
).
: Hysteresis can be set between "0" and "3% of the maximum rated flow". If the difference between the Set point 1 and
Set point 2 is less than "6% of the maximum rated flow", the maximum Set value of hysteresis is (Set point 1 - Set point 2)
divided by 2. If the hysteresis is set to greater than this value, [Error] will be displayed.
Press the
button.
Setting of Set point is completed.
Return to measurement mode.