HRX-OM-I051
Chapter 8 Appendix
HRZ Series
8.4 Offset Function
8-19
8.4.1
Example of offset function
When the discharge temperature of the circulating fluid is at 30°C, heat is
dissipated by 1°C to allow the circulating fluid in your system to be 29°C. Under
the above condition, the following process is to be performed with the utilization of
MODEs 1 to 3.
Figure 8-6 Example of Offset Function
When MODE1 is selected
This mode enables this system to exercise temperature control to obtain 31°C
(TEMP SP value +OFFSET value), with OFFSET value set at 1°C. Once the
discharge temperature of the circulating fluid becomes 31°C, 1°C-thermal
dissipation is assured to allow the circulating fluid in your system to be 30°C.
TEMP SP value is obtained for your system.
Note that “31°C” is recorded in TEMP PV and communication data.
Figure 8-7 When MODE1 is selected
1
℃
This system
Your system
Discharge temp.:
31
℃
Circulating fluid temp. in
your system: 30
℃
TEMP PV 31
℃
TEMP SP 30
℃
OFFSET 1
℃
External communication
Communication data
TEMP PV 31
℃
TEMP PV
31
℃
Heat dissipation:
1
℃
This system
Your system
Discharge temp.:
30
℃
Circulating fluid temp. in
your system: 29
℃
TEMP PV 30
℃
TEMP SP 30
℃
External communication
Communication data
TEMP PV 30
℃
Heat dissipation:
Содержание HRZ001-H
Страница 6: ...HRX OM I051 Table of Contents HRZ Series TOC 4...
Страница 40: ...HRX OM I051 Chapter 3 Transporting and Installation 3 3 Procedure for Installation HRZ Series 3 16...
Страница 46: ...HRX OM I051 Chapter 4 System Startup and Shutdown 4 5 System Startup and Shutdown HRZ Series 4 6...
Страница 62: ...HRX OM I051 Chapter 5 System Operation 5 4 Examples of System Operation HRZ Series 5 16...
Страница 66: ...HRX OM I051 Chapter 6 Error Message and Troubleshooting 6 2 Troubleshooting HRZ Series 6 4...