dV

dV

dt

dt

 = Voltage increase ratio

Time

Voltage

Caution

1. Communication cable should be prepared by the 

customer.

2. Provide a stable power supply which is not affected 

by surge or distortion.

If the voltage increase ratio (dV/dt) at the zero cross should 
exceed 40 V/200 

μ

sec., it may result in malfunction.

Piping

Caution

1.  Regarding the circulating fluid pipings, consider 

carefully the suitability for shutoff pressure, 
temperature and circulating fl uid.

If the operating performance is not suffi cient, the pipings may 
burst during operation. Also, using corrosive materials such as 
aluminium or iron for fluid contact parts such as piping may 
cause clogging or leakage in the circulating fluid and facility 
water circuits. Provide protection against corrosion when you 
use the product.

2.  Select the piping port size which can exceed the 

rated fl ow.

For the rated fl ow, refer to the pump capacity table.

3.  When tightening at the circulating fluid inlet and 

outlet, drain port or overflow port of this product, 
use a pipe wrench to clamp the connection ports.

4.  This product series are constant-temperature fluid 

circulating machines with built-in tanks.

Do not install equipment on your system side such as pumps 
that forcibly return the circulating fluid to the unit. Also, if you 
attach an external tank that is open to the air, it may become 
impossible to circulate the circulating fl uid. Proceed with caution.

Electrical Wiring

Warning

1 . Grounding should never be connected to a water 

line, gas line or lightning rod.

HRR 

Series

Specifi c Product Precautions 3

Mounting / Installation

Warning

1. Do not use the product outdoors.
2.  Do not place heavy objects on top of this product, 

or step on it. 

The external panel can be deformed and danger can result.

Caution

1 . Make sure that the rack and the rack rail can support 

the weight of the product.

2.  Refer to the Operation Manual for this product, and 

secure an installation space that is necessary for 
the maintenance and ventilation.

<Air-cooled refrigeration>

1.  The air-cooled type product exhausts heat using the fan that is 

mounted to the product. If the product is operated with 
insufficient ventilation, ambient temperature may exceed 40 

°

C, 

and this will affect the performance and life of the product. To 
prevent this ensure that suitable ventilation is available (see 
below). 

2.  For installation indoors, ventilation ports and a ventilation 

fan should be equipped as needed.

<Heat radiation amount/Required ventilation rate>

Model

Heat radiation 

amount

[kW]

Required ventilation rate [m

3

/min]

Differential temp. of 3

° 

C between 

inside and outside of installation area

Differential temp. of 6 

°

C between 

inside and outside of installation area

HRR012-A

Approx. 2

40

20

HRR018-A

Approx. 4

70

40

HRR024-A

Approx. 5

90

50

HRR030-A

Approx. 6

100

60

Be sure to read this before handling the products. Refer to the back cover for safety instructions. 
For temperature control equipment precautions, refer to the “Handling Precautions for SMC 
Products” and the “Operation Manual” on the SMC website: http://www.smc.eu

26

Rear side of the product

Front side of the product

700 mm or more

300 mm or more

Содержание HRR Series

Страница 1: ...bility Single phase 200 to 230 VAC 50 60 Hz Global power supply 1 0 1 6 2 0 2 5 kW 50 Hz Air cooled Refrigeration Cooling capacity DI filter Option Particle filter Standard Bypass valve Standard 310 m...

Страница 2: ...duct Optional Accessories Optional Accessories Cap Drain port Rc1 4 Water leakage sensor Drain pan Handle Accessory Replacement particle filter element DI filter replacement Drain pan Built in water l...

Страница 3: ...Set value displayed in green Set temperature etc is displayed Easy check from the circulation fluid level HRS012 HRR012 HRR012 HRS012 615 mm 310 mm Flow rate and pressure adjustment can be seen on th...

Страница 4: ...opens and closes to keep the refrigerant gas pressure consistent The facility water flow rate is controlled by the water regulating valve Facility water circuit Circulating fluid circuit Refrigeration...

Страница 5: ...LEVEL a WRN Alternately displayed Maintenance notification number MT01 X is displayed if a maintenance notification has occurred To menu screen REF a TEMP Alternately displayed Compressor inlet temper...

Страница 6: ...d can be output Remote operation signal input Chiller can be operated remotely by contact input signals Output setting example Output 1 Temperature rise Output 2 Pressure rise Output 3 Operation statu...

Страница 7: ...wave inspection machine Transmission cable connector for fibre laser Cooling of the laser irradiated part Temperature control of the X ray tube and X ray light sensing part Cooling of the UV lamp X r...

Страница 8: ...on Water cooled Refrigeration HRR Series Pressure Switch Monitors pressure of the circulating fluid and facility water ISE20C ISE7 G 3 Screen Display High Precision Digital Pressure Switch PSE300AC PS...

Страница 9: ...Alarm p 16 Communication Functions p 17 Thermo chiller Rack Mount Type HRR Series Options With Electric Conductivity Control Function Applicable to DI Water Piping p 19 Applicable to DI Water Piping...

Страница 10: ...pressure pump mounted U Conforming to UL Standards When multiple options are combined indicate symbols in alphabetical order Water cooledRefrigeration HRR U W 20 Pipe thread type Rc F G With Rc G conv...

Страница 11: ...of the Japan Refrigeration and Air Conditioning Industry Association JRA GL 02 1994 cooling water system circulating type make up wa ter 3 q Ambient temperature 2 5 C w Circulating fluid temperature 2...

Страница 12: ...e 2 If tap water is used use water that conforms to Water Quality Standards of the Japan Refrigeration and Air Conditioning Industry Association JRA GL 02 1994 cooling water system circulating type ma...

Страница 13: ...1500 1000 500 0 Ambient temperature or facility water temperature 32 C 25 C 40 C Circulating fluid temperature C Cooling capacity W 0 10 20 30 40 3500 3000 2500 2000 1500 1000 500 0 Ambient temperatur...

Страница 14: ...emperature or facility water temperature 40 C 32 C 25 C 5 C Circulating fluid flow rate l min Circulating fluid pressure MPa 0 5 10 15 20 25 0 3 0 2 0 1 0 Outlet 60 Hz Outlet 50 Hz Return port Allowab...

Страница 15: ...connector Product label Circulating fluid outlet Rc1 2 226 73 424 397 Ventilation air outlet Ventilation air inlet 361 4 259 8 139 1 37 5 0 86 10 440 Includes protruding parts 550 50 Maintenance port...

Страница 16: ...r Inside of the cover panel 210 38 0 424 397 164 5 140 5 0 272 5 183 6 126 4 37 5 0 440 Includes protruding parts 550 24 50 Maintenance port Power supply switch Operation display Fluid level gauge 10...

Страница 17: ...9 key Move item downward or decrease the set value 0 RESET key Reset the alarm Alarm code Alarm message Initial value Display unit Upper stage White Lower stage Green AL01 Low level in tank abnormal F...

Страница 18: ...pplication Division Initial value Default setting 1 24 VDC output Output 2 24 VDC output Output 3 24 VDC output Output 4 Contact input signal 1 Input OFF 5 Common of contact output signal 1 Output 6 C...

Страница 19: ...D 3 SG 5 This product RD 2 SD 3 SG 5 D sub 9 pin female socket type Communication connector 5 1 9 6 Run Stop Circulating fluid temperature setting Writing Circulating fluid discharge temperature Circu...

Страница 20: ...ng fluid circuit is made from non copper materials Available DI water is electric conductivity 2 S cm or more Electric resistivity 0 5 M cm or less This Option M does not have electric resistance elec...

Страница 21: ...p Capacity HRR012 018 024 030 20 MT HRR012 018 024 030 20 T Applicable model HRR012 018 024 030 20 T HRR012 018 024 030 20 MT 1 Pump Rated flow 50 60 Hz 2 3 l min 10 0 42 MPa 14 0 40 MPa 10 0 32 MPa 1...

Страница 22: ...rtridge Element for the maintenance of the particle filter for circulating fluid DI filter cartridge for replacement for Option DM Electric conductivity control type DI water piping type Part number A...

Страница 23: ...ser s equipment Q qm x C x T2 T1 x qv x C x T 60 1 x 10 x 4 2 x 103 x 2 0 60 1400 J s 1400 W Cooling capacity Considering a safety factor of 20 1400 W x 1 2 1680 W Heat generation amount by user s equ...

Страница 24: ...the circulating fluid discharge pressure Consider the installation height difference between the thermo chiller and the user s equipment and the piping resistance such as circulating fluid pipings or...

Страница 25: ...arts such as piping may cause clogging or leakage in the circulating fluid circuit Therefore take sufficient care when selecting fluid contact part materials such as piping 4 Design the piping so that...

Страница 26: ...he descriptions in the ta ble below Select the thermo chiller considering the descriptions qUpper limit of ambient temperature Use the product in ambient temperature of the described value or low er a...

Страница 27: ...be connected to a water line gas line or lightning rod HRR Series Specific Product Precautions 3 Mounting Installation Warning 1 Do not use the product outdoors 2 Do not place heavy objects on top of...

Страница 28: ...iping due to metal ion 5 Do not use fluid that includes metric powers and other foreign materials It can cause issues clogging of the circulating fluid circuit or leakage Warning HRR Series Specific P...

Страница 29: ...er once again when the fluid level is reduced When there is no reduction in the fluid level the job of removing the air is completed 2 Confirmation during operation Check the circulating fluid tempera...

Страница 30: ......

Страница 31: ...nergy railways air navigation space shipping vehicles military medical treatment combustion and recreation or equipment in contact with food and beverages emergency stop circuits clutch and brake circ...

Отзывы: