5.12
Register Map
5-15
5.12.10 Data instruction
In the Ethernet mode, selected data is displayed in the data instruction
1, 2, 3, 4 by assigning the data instruction.
For the data that can be displayed and the instruction method, refer to
"3.13.10 Data instruction" of serial communication.
5.12.11 Product number
Reads the product number of this product.
■
Communication example
○
When reading the product number and serial number
〇
Unit identifier
:
1
○
Function code 04
:
Read 19 consecutive data from register 005h.
Product number HRL300-A-40
Serial number
:
AA001
Required message010400500013
Field name
Example
(HEX)
Binary data
Unit identifier
0x01
0x01
Function
0x04
0x04
First address of the specified
register
0x0050
0x00,0x50
Number of registers to be read
0x0013
0x00,0x13
―
Total
quantity
of byte
6