Chapter 5 Ethernet Modbus / TCP communication
HRL Series
5.4
Communication specification
5-3
5.4 Communication specification
Table 5.4-1
Ethernet Modbus/TCP communication specification
Item
Specification
Connector type (for the product) RJ45
Communication style
Ethernet
Data transfer method
100BASE-TX/10BASE-T
Protocol
Modbus/TCP*1
1
:
Refer to Modicon Co. protocol specifications "PI-MBUS-300 Rev.J".
Table 5.4-2
Ethernet Modbus/TCP communication Parameter
Item
Setting range
Initial value
IP Address
0.0.0.0
~
223.255.255.255
192.166.0.40
Subnet mask
0.0.0.0
~
255.255.255.255
255.255.255.0
Default gateway
1
0.0.0.0
~
255.255.255.255
0.0.0.0
Port No.
―
502
1
:
When default gateway is not used, the value should be set to 0.0.0.0.
5.5 Modbus/TCP communication function
Modbus protocol is a communication protocol developed by Modicon.
It is used to communicate with a PC or PLC.
Register content is read and written by this communication protocol.
This communication has the following features.
・
Controls run/stop.
・
Sets and reads the circulating fluid set temperature.
・
Reads the circulating fluid discharge temperature.
・
Reads the circulating fluid discharge pressure.
・
Reads the circulating fluid flow rate.
・
Reads the circulating fluid electric conductivity(CH2 only).
・
Reads the condition of the product.
・
Reads the alarm generating condition of the product.
・
The operation mode can be switched to "SERIAL" mode.
・
You can reset the alarm.
Refer to “5.12 Register Map” for the register of the product.