4  Startup and Shutdown 

 

HRG001-W HRG002-W HRG005-W   

4.4 Check at startup 

1

st

 edition :Jul. 2005 

4-5

Fig. 4-5    Bypass valve (HRG001-W / HRG002-W) 

Fig. 4-6    Bypass valve (HRG005-W) 

 

4.4  Check at startup 

Check the following items at startup of the unit. 

 

 

 

 

 

z

 

No leak from circulating fluid piping 

z

 

No circulating fluid flowing out of the tank drain port 

z

 

Circulating fluid pressure within the specified range 

 

„

 

Bypass valve 

Normally, the bypass valve is fully opened. If the unit is started up with the 
valve fully closed, water supply may reach abnormal high pressure 
depending on external piping conditions. Be sure to keep the bypass valve 
fully opened for initial startup of the unit installed. 

Adjust the bypass valve to obtain required pressure and flow rate by 

checking on the external pressure gauge and flow meter that can be 
prepared by customer or mounted on external piping. 

 

 

 

 

 

 

 

 

 

 

 

 

 

When any abnormality is found, press the [OFF] switch immediately to 
stop the unit and turn the power supply breaker off. 

Bypass valve 

Right 

Right 

Содержание HRG001-A

Страница 1: ...st edition Jul 2005 Rev A Sep 2006 Operation Manual Water refrigerated Thermo cooler HRG001 W HRG002 W HRG005 W SMC Corporation Save This Manual Carefully for Use at Any Time 2005 SMC CORPORATION All Rights Reserved ...

Страница 2: ...nual are qualified to perform the installation and operation of the unit This manual attached to the unit and its contents will not be a part of contract and accompany modification or change of existing agreement commitment or relation All SMC s obligation is covered by Sales Agreement which is only document to guarantee the content described on the agreement Any description of this manual will no...

Страница 3: ... 1 7 1 5 1 Recovery of refrigerant and compressor oil 1 7 1 5 2 Disposal of unit 1 7 2 Descriptions of Components 2 1 2 1 APPEARANCE OF UNIT 2 1 2 1 1 HRG001 W HRG002 W 2 1 2 1 2 HRG005 W 2 1 2 2 DESCRIPTIONS AND FUNCTIONS OF COMPONENTS 2 2 2 2 1 HRG001 W HRG002 W 2 2 2 2 2 HRG005 W 2 3 2 2 3 Control panel 2 4 3 Transport and Installation 3 1 3 1 TRANSPORT 3 1 3 2 INSTALLATION 3 3 3 2 1 Installati...

Страница 4: ...ing the unit 4 4 4 4 CHECK AT STARTUP 4 5 5 Error Message and Troubleshooting 5 1 5 1 ERROR MESSAGE 5 1 5 2 TROUBLESHOOTING 5 2 6 Unit Maintenance 6 1 6 1 CONTROL OF WATER QUALITY 6 1 6 2 INSPECTION AND CLEANING 6 2 6 2 1 Daily inspection 6 3 6 2 2 Monthly inspection 6 4 6 2 3 Biannual inspection 6 4 6 3 STORAGE 6 5 6 4 CONSUMABLES 6 5 7 Documents 7 1 7 1 SPECIFICATIONS LIST 7 1 7 2 OUTLINE DIMENS...

Страница 5: ...derstand the safety related items in this manual before working with this unit z This manual is not for comprehensive safety and hygiene education Such a manual should be provided by a safety training manager z All personnel who work on or around this unit are to have proper training and education on dangers specific to this unit and safety measures against potential hazards z A safety manager is ...

Страница 6: ...us injury and minor injury Serious injury This term describes injuries such as loss of eyesight wound burns electrical shock fracture toxication that leaves aftereffects which may require prolonged treatment and hospitalization Minor injury This term describes injuries that do not require prolonged treatment or hospitalization injuries other than serious injuries described above DANGER means that ...

Страница 7: ...ls in easy to understand manner Symbol of electrical hazard Symbol of heat hazard Symbol of rotating shaft hazard Symbol of Don ts Symbol of Dos This symbol denotes the items that must not be implemented This symbol denotes the obligation items which you must follow in operation of this unit This symbol warns you of possible risk of electrical shock This symbol warns you of potential burns This sy...

Страница 8: ...may cause the operator to get the finger caught in these parts The attached label contains the symbol Do not operate the unit without the cover panel mounted The unit contains the power supply carrying high voltage inside that is isolated with the cover panel Unit operation without the cover panel allows the high votage to apply outside and cause injuries Only trained personnel are allowed to work...

Страница 9: ...05 1 5 1 3 2 Type of hazard warning labels Warning label on the front panel Fig 1 1 Warning label on the front panel Warning label for high voltage Fig 1 2 Warning label for high voltage Do not remove or deface the warning labels Read the contents of the hazard warning labels with care to keep them in mind ...

Страница 10: ...rning label 1 4 Model label Check the model no described on the label Fig 1 4 Location of model label Front Warning label for high voltage Warning label on the front panel z Recognize where the hazard warning labels are attached z The user is not allowed to reposition the labels If the label is replaced due to being peeled off or worn out keep the previous position Front ...

Страница 11: ... laws and regulations Remarks The type and amount of used freon can be found on the label Only service personnel or qualified personnel are allowed to open the cover panel of the unit Only personnel with sufficient knowledge and experiences with the unit and associated equipment are allowed to recover refrigerant and compressor oil Do not mix the compressor oil with domestic waste for disposition ...

Страница 12: ...HRX OM J022 1 Safety Instructions 1 5 Disposition of waste HRG001 W HRG002 W HRG005 W 1 st edition Jul 2005 1 8 ...

Страница 13: ... 1 Appearance of unit 1 st edition Jul 2005 2 1 2 Descriptions of Components 2 1 Appearance of unit 2 1 1 HRG001 W HRG002 W Fig 2 1 Appearance of unit HRG001 W HRG002 W 2 1 2 HRG005 W Fig 2 2 Appearance of unit HRG005 W Front Right Back Left Top Right Back Top Left Front ...

Страница 14: ...G002 W Fig 2 3 Piping connection port HRG001 W HRG002 W Y strainer 1 2 Top Front Left Right 4 φ13 For anchor bolt Tank drain port Rc1 2 Port for overflow Rc1 2 Circulating fluid return Rc1 2 Bypass valve Circulating fluid OUT Rc1 2 Tank lid Level indicator Control panel Electrical unit Power cable access Filmed grommet Single cable access Filmed grommet Cooling water OUT Rc1 2 Cooling water IN Rc1...

Страница 15: ...005 W Y strainer 1 2 Top Front Left 4φ13 for anchor bolt Tank drain port Rc1 2 plugged Cooling water IN Rc1 2 Port for overflow Rc1 2 Bypass valve Circulating fluid OUT Rc1 2 Supply port Rc1 2 Level indicator Control panel Electrical unit Power cable access Filmed grommet Signal cable access Filmed grommet Circulating fluid return Rc1 2 Eye bolt M12 Cooling water OUT Rc1 2 Tank lid Right ...

Страница 16: ... a circulating fluid 1 Digital display PV SV SV Indicates set temperature of a circulating fluid 2 POWER LED Lights up when the power is supplied 3 RUN LED 4 PUMP LED Lights up when the ON switch is pressed 5 ALARM LED Lights up when an alarm arises 6 ON switch This is used to run the unit 7 OFF switch This is used to stop the unit 8 MODE key This is used to switch the screens between PV and SV 9 ...

Страница 17: ...t maintenance possibly exposed to dangerous situations z If eyebolts are used for lifting ensure the unit is held at four points z Keep each eyebolt at an angle from 45 to 60 degrees with repect to the postion of the center of gravity when lifting the unit If the forklift is used for transporting ensure that the fork is inserted in a place as specified in Fig 3 1 Fork insertion position and unit l...

Страница 18: ...ul 2005 3 2 Fig 3 1 Fork insertion position and unit lifting HRG001 W HRG002 W HRG005 W Lifting position Approx 60deg Approx 60deg Fork insertion position Fork insertion position Fork insertion position Fork insertion position Fork insertion position Fork insertion position Fork insertion position ...

Страница 19: ... z Environment that generates strong high frequencies z Environment at high altitudes of over 1000m z Condition which allows strong vibrations and impacts to transmit to the unit z Condition with external force or load to deform the unit z Condition with an insufficient maintenance space as required z Condition with an insufficient maintenance space as required Do not install the unit in a place p...

Страница 20: ...for safety Wiring installation with the unit energized is strictly prohibitted z Use the specified cables Properly apply strain relief to prevent an external force from being exerted on the terminals Poor or loose connection can cause electrical shock heat spots or fire z Supply the power to the unit from a reliable power source without surge voltage z Be sure to use a GFCI breaker to prevent an e...

Страница 21: ...panel 2 Connect the power supply cable and signal cable as shown in the figure Fig 3 2 Removal of front panel Fig 3 3 Electrical wiring HRG001 W HRG002 W Fig 3 4 Electrical wiring HRG005 W Front panel Screw Screw Front Power supply cable entry Signal cable entry Front Signal cable Power supply cable Signal cable entry Front Power supply cable entry Signal cable Power supply cable ...

Страница 22: ... open closed for error Operation signal output relay contact normally close opened for error Operation signal output circuit I O board Error detected stop signal output circuit Remote operation input circuit FG Frame ground Electrical circuit Power supply box User s preparation Power supply cable Signal cable ELB Current leakage breaker Remote operation signal input DC 24V input DC 0V input Error ...

Страница 23: ...ic wrench and tighten the pipe Fig 3 7 Tightening of pipe Remarks Install a valve at the drain port to facilitate the draining of the circulating fluid from the tank The vavle needs to be preapred separately Connected port 29 4N m or less z Install piping properly Improper installation may cause leaks z Keep supply water pressure below 0 5MPa z Make sure the locations of IN and OUT ports for circu...

Страница 24: ...ly the circulating fluid until the fluid reaches the range specified on the level indicator Fig 3 9 Level indicator Keep the fluid level in the tank between HIGH and LOW If the fluid is out of the range the circulating fluid may overflow that results in a ground falut Fig 3 8 Recommended piping installation Load device Drain pit Circulating fluid OUT Circulating fluid return Tank drain port Port f...

Страница 25: ...cording to the procedures described below and in Chapter 3 Disconnection of power supply cable Be sure to cut off the power supply when disconnecting the power supply cable If the unit is relocated only personnel with knowledge of the unit and associated equipment are allowed to perform unit reinstallation Precautions described below must always be followed z Only qualified personnel are allowed t...

Страница 26: ...HRX OM J022 3 Transport and Installation 3 2 Installation HRG001 W HRG002 W HRG005 W 1 st edition Jul 2005 3 10 ...

Страница 27: ...Connection of cable Check that the power cable ground and I O signal cables are correctly connected 4 1 3 Piping for cooling water Check that piping for cooling water IN and OUT are correctly connected 4 1 4 Piping for circulating fluid Check the I O piping of the circulating fluid is installed correctly 4 1 5 Level indicator for level in the tank Check the fluid level is within the specified rang...

Страница 28: ... z The digital display PV lights up and displays temperature of the circulating fluid z The ALARM LED lights up and goes out in 5 sec Fig 4 1 Power supply 4 2 2 Setting of circulating recirculating fluid temperature Press the UP and DOWN keys to set a desired temperature in the digital display SV Fig 4 2 Setting of circulating fluid temperature z Note Circulating fluid setting temp range is 5 to 3...

Страница 29: ...uid circuit at initial startup Remove the front panel and purge air according to the procedures given below 1 Press the TS switch for a several seconds monitoring the fluid level gauge Air is purged from the pipe and the fluid level is lowered 2 Supply the circulating fluid again according to section 3 2 5 Fig 4 3 TS switch ポンプ単独運転 switch TS switch Front If leakage occurs due to faulty piping incl...

Страница 30: ...h on the control panel The unit starts operating and regulates the circulating fluid temperature The RUN LED and PUMP LED on the control panel come on Fig 4 4 Starting the Unit 4 3 2 Stopping the unit 1 Press the OFF switch on the control panel The unit stops The RUN LED and PUMP LED on the control panel go out Fig 4 5 Stopping the unit RUN LED PUMP LED ON switch RUN LED PUMP LED OFF switch ...

Страница 31: ...ss valve Normally the bypass valve is fully opened If the unit is started up with the valve fully closed water supply may reach abnormal high pressure depending on external piping conditions Be sure to keep the bypass valve fully opened for initial startup of the unit installed Adjust the bypass valve to obtain required pressure and flow rate by checking on the external pressure gauge and flow met...

Страница 32: ...HRX OM J022 4 Startup and Shutdown 4 4 Check at startup HRG001 W HRG002 W HRG005 W 1 st edition Jul 2005 4 6 ...

Страница 33: ...tatus POWER RUN ALARM Operation signal output Error stop signal output Power error Stopped Open contact Closed contact Start up failure Stopped Green Red Open contact Open contact Reverse of pump and compressor Stopped Green Red Open contact Open contact Tank water level drop Lower limit of water level in the tank Stopped Green Red Open contact Open contact Pump overload Stopped Green Red Open con...

Страница 34: ...valve Ask for service Pump overload Pump thermal overload switch has been tripped Abnormal failure of pump Change the pump Ask for service Manual reset Power voltage sag Normal according to product spec Boost up the capacity of power breaker Wiring should be performed by a qualified person Abnormal heat dissipation capability of condensor Normal according to product spec Improve ambient conditions...

Страница 35: ...elow Residual chlorine mgCl L 0 3 and below Reference Free carbon dioxide mgCO2 L 4 0 and below Excerpt from the Refrigeration and Air Conditioning Equipment Water Quality Guideline JRA GL 02 1994 circulating fluid used in this unit is fresh water tap water This unit may be damaged when unpermitted fluids are used Potential fluid leak may occur if disregarded which results in electric shock and gr...

Страница 36: ...s and do not touch any electrical components such as a power supply plug It may cause an electric shock if disregarded Keep this unit from water Do not wash the unit with water It may cause an electric shock and fire if disregarded Do not touch the fin directly during cleaning of the condenser It may cause personal injury if disregarded Always mount the panel back onto the unit after removing the ...

Страница 37: ...f the range replenish or drain excess circulating fluid to maintain a proper level Be sure to stop the unit before replenishing the circulating fluid z The characters and numbers on the liquid crystal display of the control display panel should be clear z There should be no leak from the circulating fluid piping z Water supply pressure of the circulating fluid should be within the specified range ...

Страница 38: ...It has a foul odor z The water has been discolored 6 2 3 Biannual inspection Check for leak from the pump mechanical sealing Remove the panel and check for leak from the pump mechanical sealing When a leak is found it is necessary to replace the mechanical sealing Contact the local distributor or SMC s sales branch I m p o r t a n t z Leak from the mechanical sealing Leakage from the mechanical se...

Страница 39: ... valve and drain the water from the tank 3 Remove the drain plug of the circulating pump and drain the water from the pump 4 Cover the unit with a plastic sheet for storage after draining is completed 6 4 Consumables Replace parts in response to the level of wearing out at inspection Table 6 2 Biannual inspection Part number Part Qty Remarks HRG S0003 Pump mechanical seal 1 set For HRG005 It is no...

Страница 40: ...HRX OM J022 6 Unit Maintenance 6 4 Consumables HRG001 W HRG002 W HRG005 W 1 st edition Jul 2005 6 6 ...

Страница 41: ...evel switch Pump reverse rotation detection with phase relay Pump compressor reverse rotation detection with phase relay Unit stop function for pump compressor overload with over current relay Unit stop function for abnormal fan motor temperature rise Temp fuse is built into fan motor Unit stop function for abnormal fan motor temperature rise Thermostat is built in fan motor Emergency stop Unit st...

Страница 42: ...ns HRG001 W HRG002 W HRG005 W 1 st edition Jul 2005 7 2 7 2 Outline dimensions 7 2 1 HRG001 W and HRG002 W Fig 7 1 Outline dimensions HRG001 W HRG002 W 7 2 2 HRG005 W Fig 7 2 Outline dimensions HRG005 WW Top Front Right Left Top Front Right Left ...

Страница 43: ... J022 7 Documents HRG001 W HRG002 W HRG005 W 7 3 Electric circuit diagram 1 st edition Jul 2005 7 3 7 3 Electric circuit diagram 7 3 1 HRG001 W and HRG002 W Fig 7 3 Electric circuit diagram HRG001 W HRG002 W ...

Страница 44: ...HRX OM J022 7 Documents 7 3 Electric circuit diagram HRG001 W HRG002 W HRG005 W 1 st edition Jul 2005 7 4 7 3 2 HRG005 W Fig 7 4 Electric circuit diagram HRG005 W ...

Страница 45: ... T Tank LS Level switch LI Limnimeter PM Pump TI Temperature sensor Water feed circuit RV Hand valve Over flow port Circulating fluid OUT Circulating fluid return Tank drain port Cooling water IN Cooling Water OUT Sym bol Name PV Pressure water regulating valve Cooling water circuit S Strainer CM Compressor CD Air cooled condenser HPS Pressure switch for high pressure D Refrigerant dryer EV Evapor...

Отзывы: