HRX-OM-J022
3 Transport and Installation
3.2 Installation
HRG001-W HRG002-W HRG005-W
1
st
edition : Jul. 2005
3-8
Recommended piping installation
No.
Name
Size
1 Valve
Rc1/2
2 Y-shaped
strainer
Rc1/2
3
Relieving valve
Rc1/2, set from 0 to 0.5 MPa
4
Pressure gauge
0 to 1.0 MPa
5
Flow meter
0 to 50 L/min
3.2.5
Supply of circulating fluid
1.
Open the tank lid and supply the circulating fluid until the fluid reaches the range
specified on the level indicator.
Fig. 3-9 Level indicator
Keep the fluid level in the tank between “HIGH” and “LOW”. If the fluid
is out of the range, the circulating fluid may overflow that results in a
ground falut.
Fig. 3-8 Recommended piping installation
Load device
Drain pit
Circulating fluid OUT
Circulating fluid return
Tank drain port
Port for overflow
Cooling water IN
Cooling water OUT
HIGH
LOW
HIGH
LOW
HRG001-A & HRG002-A
HRG005-A
Level range
Opening for level check
Opening for level check
Level range