Appendix A. Useful Features 

Appendix A.1. BACnet Object Names 

When an external BACnet Client builds a list of Object Names, the BACnet Server Map Descriptor names 
determine the BACnet Object Name. If the Map Descriptor length is greater than 1, the Object Name will 
be  suffixed  with  the  index  into  the  Map  Descriptor.  For  example,  if  the  Map  Descriptor  name  is 
SMD_AI_01  and  the  length  3,  then  the  Object  Names  will  be  SMD_AI_01[0],  SMD_AI_01[1]  and 
SMD_AI_01[2]. 

Appendix A.2. Network Number 

If  multiple  BACnet  Nodes  are  specified  on  the  Server  side,  the  FieldServer  automatically  defaults  to 
virtual operation. In effect, the FieldServer simulates a software router. BACnet identifies this FieldServer 
using  a  combination  of  its  network  number  and  IP/MAC  address.  The  default  Network  number  of  a 
FieldServer  is  5.  If  there  is  more  than  one  FieldServer  on  a  BACnet  intranet  with  multiple  nodes,  the 
default  network  number  of  the  additional  FieldServers  will  need  to  be  changed  and  a  unique  number 
allocated to each.  

A unique network number will need to be assigned if 

both

 of the following conditions are true: 

 

The FieldServer has multiple BACnet Server nodes. 

 

There is more than one FieldServer on a network which includes multiple BACnet nodes. 

To override the FieldServer’s default network number 5 include the following in the configuration file: 

Section Title 

Bridge 

Column Title 

Function 

Legal Values 

Title 

FieldServer name. 

Text 

 

Network_Number* 

Specify  a  unique  network  number  if  there  are  multiple  virtual 
Server nodes. 

1-65534, 

 

Example 

//    FieldServer Driver specific parameters  
 

 

Bridge 

 

Title 

, Network_Number 

BACnet Server 

, 6 

 

NOTE:  While it is theoretically possible to have up to 65535 virtual nodes, it is recommended that 

a maximum of 32 is configured. If an application requires the configuration of more than 
32 virtual nodes, consult Sierra Monitor technical support. 

 

Содержание FieldServer FS-8700-16 BACnet PTP

Страница 1: ...on 2 01 Document Revision 1 B FieldServer FS 8700 16 BACnet PTP Serial Driver Manual Supplement to the FieldServer Instruction Manual APPLICABILITY EFFECTIVITY Effective for all systems manufactured a...

Страница 2: ...support needs related to the FieldServer product Sierra Monitor Corporation 1991 Tarob Court Milpitas CA 95035 Website www sierramonitor com U S Support Information 1 408 964 4443 1 800 727 4377 Email...

Страница 3: ...6 Appendix A 1 BACnet Object Names 16 Appendix A 2 Network Number 16 Appendix A 3 Accessing Data from BACnet Properties Comprising Arrays of Values 17 Appendix A 4 FieldServer Implementation of BACnet...

Страница 4: ...7 Appendix C 3 Liebert 27 Appendix C 4 Automated Logic Corporation 27 Appendix C 5 Honeywell EBI 27 Appendix D Reference 28 Appendix D 1 Object_Type Legal Values Abbreviation Descriptions 28 Appendix...

Страница 5: ...device starts control related communications with another it needs to obtain some of the information presented by the other device s Device Object Unlike other Objects the Device Object s Instance nu...

Страница 6: ...TO COLOUR RX RJ45 01 DB9M 02 GREY CTS RJ45 02 DB9M08 BROWN DSR RJ45 03 DB9M 06 YELLOW GND RJ45 04 DB9M 05 GREEN GND RJ45 05 RED TX RJ45 08 DB9M 03 BLUE RTS RJ45 07 DB9M 07 ORANGE DTR RJ45 06 DB9M 04 B...

Страница 7: ...Legal Values Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Array_Format Provide data format Each Data Array can only take on one format Float Bit Byte Uint16 Uint3...

Страница 8: ...required from the Servers needs to be mapped in the Client Side Map Descriptors section Details on how to do this can be found below NOTE In the following tables indicates an optional parameter and b...

Страница 9: ...xample Client Side Nodes Nodes Node_Name Node_ID Protocol Port Retries DEV_1 1 BACnet_PTP P1 2 5 4 Map Descriptor Parameters Column Title Function Legal Values Map_Descriptor_Name Name of this Map Des...

Страница 10: ...turn the total number count of array items linked to the property If the parameter is not specified a list of all items will be returned Refer to Appendix A 3 0 to max number of array items in the BAC...

Страница 11: ...DEV_1 AO 1 Present_Value 30 000s CMD_AO_02 DA_AO_01 1 Rdbc DEV_1 AO 2 Present_Value 30 000s CMD_AO_03 DA_AO_01 2 Rdbc DEV_1 AO 3 Present_Value 30 000s Map_Descriptors Map_Descriptor_Name Data_Array_N...

Страница 12: ...ptors section Details on how to do this can be found below NOTE In the tables below indicates an optional parameter with the bold legal value as default 6 1 Driver Specific FieldServer Parameters Sect...

Страница 13: ...D Protocol 4 Virtual_DEV_11 11 BACnet_PTP 6 4 Server Side Map Descriptor Parameters 6 4 1 FieldServer Specific Map Descriptor Parameters Column Title Function Legal Values Map_Descriptor_Name Name of...

Страница 14: ...to be returned as Present_Value on startup or when control is relinquished Must be specified for outputs Refer to Appendix D 2 Any Float value Length Used to create an array of sequential Object_Inst...

Страница 15: ..._AO_01 DA_AO_01 0 Passive Virtual_DEV_11 AO 1 percent relative humidity SMD_AO_02 DA_AO_01 1 Passive Virtual_DEV_11 AO 2 percent relative humidity SMD_AO_03 DA_AO_01 2 Passive Virtual_DEV_11 AO 3 perc...

Страница 16: ...there is more than one FieldServer on a BACnet intranet with multiple nodes the default network number of the additional FieldServers will need to be changed and a unique number allocated to each A un...

Страница 17: ...highest value from the Priority Array Table is stored to the Data Array If all values have been Relinquished from the Priority Array Table then the Map Descriptors Relinquish Default value will be sto...

Страница 18: ...ble set up a look up table Offset_Table Offset_Table_Name Table_String Table_Index_Value FIRE_ALRM_TEXT SYSTEM READY 1 FIRE_ALRM_TEXT ALARM 2 FIRE_ALRM_TEXT MAINTENANCE 3 FIRE_ALRM_TEXT OFF LINE 4 FIR...

Страница 19: ...ues in its row 0 normal 1 alarm 2 fault set up a look up table Offset_Table Offset_Table_Name Table_String Table_Index_Value Table_User_Value FIRE_ALRM_TEXT SYSTEM READY 1 0 FIRE_ALRM_TEXT ALARM 2 1 F...

Страница 20: ...set to 1 If length is not specified then it defaults to 1 so this is only a problem where length has been specified as greater than 1 The Node_Option parameter can be configured to enable or disable...

Страница 21: ...jects Map_Descriptors Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function Node_Name Object_Type Object_Instance Ack_Required SMC_NC_01 DA_NC_01 0 Passive Virtual_DEV_11 NC 1 Yes SMC_NC_02 D...

Страница 22: ...re are three options for translating these conditions to BACnet Reliability values Track_Object_Status The Reliability property mirrors the internal data object state i e if the Remote Server Node is...

Страница 23: ...val o Timeout o Length Any number of Linked Map Descriptors specifying additional objects and data array locations to be included in the transaction Each Linked Map Descriptor is specified with the fo...

Страница 24: ...3 Device Max_Master Passive_Client DA RPM 0 N1 1 CMD RPM 4 Device Max_Info_Frames Passive_Client DA RPM 1 N1 1 CMD RPM 2 AO Passive_Client DA RPM 2 N1 1 CMD RPM 1 AO Passive_Client DA RPM 6 N1 1 Addr...

Страница 25: ...d to store Map Descriptors that have the active inactive text parameters specified If the defaults are appropriate do not specify these parameters This will save memory and allow more Map Descriptors...

Страница 26: ...n error 15 Missing required parameter 16 No objects of specified type 17 No space for object 18 No space to add list element 19 No space to write property 20 No vt sessions available 21 Property is no...

Страница 27: ...olling BACnet addresses that are not configured for Liebert systems may cause the connection to fail in older versions of Liebert Please contact your Liebert supplier for more information Appendix C 4...

Страница 28: ...l about the Object Out_of_service The Out_Of_Service property of type BOOLEAN is an indication whether TRUE or not FALSE the physical input that the object represents is not in service This means that...

Страница 29: ...nd shall be less than or equal to 127 If the Max_Master property is not writeable via BACnet services its value shall be 127 Max_Info_Frames Relevant to BACnet MS TP Device Object Type The Max_Info_Fr...

Страница 30: ...cubic meters per hour Volumetric Flow cubic meters per minute Volumetric Flow cubic meters per second Volumetric Flow currency1 Currency currency10 Currency currency2 Currency currency3 Currency curr...

Страница 31: ...Enthalpy kilobecquerels Other kilo btus Energy kilo btus per hour Power kilograms kg Mass kilograms per cubic meter Other kilograms per hour Mass Flow kilograms per kilogram Other kilograms per minute...

Страница 32: ...Other milligrams per gram Other milligrams per kilogram Other milligrams per liter Other milligray Other milliliters Volume milliliters per second Volumetric Flow millimeters Length millimeters of me...

Страница 33: ...Area square meters Area square meters per Newton Other standard cubic feet per day Volumetric Flow teslas Electrical therms Energy thousand cubic feet per day Volumetric Flow thousand standard cubic f...

Страница 34: ...pported Data was requested but the response would have exceeded the maximum size of the APDU and could not be sent using an un segmented message This is not an error the BACnet client will use a diffe...

Отзывы: