BACnet PTP Serial Driver Manual
Page 14 of 34
6.4.2 Driver Specific Map Descriptor Param eters
Column Title
Function
Legal Values
Node_Name
Name of Node to fetch data from.
One of the Node Names specified
in “Server Side Node Descriptors”
Object_Type
(Alias = Data_Type)
Data type in Controller.
AI, AO, AV, BI, BO, BV, MI, MO,
MV, NC. Refer to
Object_Instance
(Alias = Address)
Instance of the Object on the Device.
0, 1, 2, 3, …4194303
Units*
The object units.
m2
Data_Array_Low_Scale*
Scaling zero in Data Array.
-32767 to 32767,
0
Data_Array_High_Scale* Scaling max in Data Array.
-32767 to 32767,
100
Node_Low_Scale*
Scaling zero in Connected Node.
-32767 to 32767,
0
Node_High_Scale*
Scaling max in Connected Node.
-32767 to 32767,
100
Active_Text
5
*
Specify the Active Text property of the
Object.
Any text string of length up to 40
characters,
Active
Inactive_Text
Specify the Inactive Text property of
the Object.
Any text string of length up to 40
characters,
Inactive
Relinquish_Default
Specify the value to be returned as
Present_Value on startup or when
control is relinquished. Must be
specified for outputs. Refer to
Any Float value
Length*
Used to create an array of sequential
Object_Instances on an Object_Type.
1 to max point count of the
FieldServer,
1
Notification_Class*
Specify the Mapdescriptor_Name of
the Notification_Class Object that
manages Intrinsic Reporting for this
Map Descriptor. Refer to
One of the configured
Mapdescriptor_Names of type NC
(Notification Class). Objects are not
available to any NC if left out.
Ack_Required*
For a Notification_Class Object,
specify whether EventNotifications
require a user Acknowledgement.
Refer to
Yes,
No
COV_Increment*
For a Server Map Descriptor of type
AO or AI, initialize the
COV_Increment property. Refer to
Any Float value,
0
Input_alarm_State*
For binary points the user can specify
which of the states (0 or 1) to regard
as an alarm state.
0,
1
Description*
Specify the
object’s description
property. E.G. Room Temp
– Refer to
Any text string of length up to 40
characters, if not configured,
defaults to Object_Name.
5
See the BACnet DFS to determine if a particular object supports this property.