Example
// Server Side Connections
Connections
Port
, Baud , Parity , Data_Bits , Stop_Bits , Protocol
P1
, 9600 , Even
, 7
, 1
, BACnet_PTP
6.3
Server Side Node Parameters
Section Title
Nodes
Column Title Function
Legal Values
Node_Name
3
Provide name for node.
Up to 32 alphanumeric characters
Node_ID
BACnet station address of physical Server node. 1 - 16777215
Protocol
Specify protocol used.
BACnet_PTP
Node_Option
Enable or disable COV for this node.
COV_Enable
, COV_Disable
Example
// Server Side Nodes
Nodes
Node_Name
, Node_ID , Protocol
4
Virtual_DEV_11 , 11
, BACnet_PTP
6.4
Server Side Map Descriptor Parameters
6.4.1 FieldServer Specific Map Descriptor Param eters
Column Title
Function
Legal Values
Map_Descriptor_Name
Name of this Map Descriptor. This is used
for Object_Name Property. Refer to
Up to 32 alphanumeric
characters
Data_Array_Name
Name of Data Array where data is to be
stored in the FieldServer.
One of the Data Array names
from
Section
Data_Array_Offset
Starting location in Data Array.
0 to (“Data_Array_Length” -1) as
specified in
Section
Function
Function of Server Map Descriptor.
Passive
3
When using the Trane Tracer Summit Workstation System, this name will appear as the object name.
4