-87-
No.EX
※※
-OMZ0016
Item
Resister
area
Bit
No.
Content of diagnostics
Diagnosed area and
processing upon error
How to
reset
Reset conditions
Remarks
(LED indications,
etc.)
Item
Details
Effective
diagnostic
coverage
I/O
processing
upon
diagnosis
System
diagnosis
2
RWr1
12
Connection
failure between
units (when
power is
supplied)
An error has
occurred in the
communication
between the wireless
unit and EX600 I/O
units.
Unit
Stop (HOLD)
Turn
the
power
on
again.
Confirm that there is no
loose connection
between the EX600 I/O
units, and connect them
correctly.
Base
W-MS: Flashes red
Remote (EX600-W)
MS: Flashes red
13 Reserved
-
-
-
-
-
-
14
Detection of
system error
(when power is
supplied)
An unrecoverable
error has occurred in
the system.
Unit
Stop (HOLD)
Manual
reset
Supply power again. If
the error persists after
resupplying power,
contact your SMC sales
representative.
Base
MS: Lights up red
Remote
MS: Lights up red
15
Detection of
hardware error
(during
operation)
An unrecoverable
error has occurred in
the hardware.
Unit
Stop (HOLD)
Manual
reset
Supply power again. If
the error is not restored
after resupplying power,
contact your SMC sales
representative.
Base
MS: Lights up red
or
W-MS: Lights up
red
Remote
MS: Lights up red
System
diagnosis
3
RWr2
0
Number of
inputs/outputs
setting error
The number of
occupied
inputs/outputs of the
Remote has
exceeded the set
value.
System
Continue
Manual
reset
Change the user set
value. Or, adjust the unit
configuration so that the
number of occupied
points is within the set
value.
Base
W-MS: Flashes red
Remote
MS: Flashes red
1
Reserved
-
-
-
-
-
-
2
Reserved
-
-
-
-
-
-
3
Reserved
-
-
-
-
-
-
4
Reserved
-
-
-
-
-
-
5
Reserved
-
-
-
-
-
-
6
System Error
detected
Memory read/write
error
System
Continue
Manual
reset
Initialize the product. If
the error persists after
resupplying power,
contact your SMC sales
representative.
Base, Remote
MS: Flashes red
7
Detection of
hardware error
Memory write error
System
Continue
Manual
reset
Initialize the product. If
the error persists after
resupplying power,
contact your SMC sales
representative.
Base, Remote
MS: Flashes red