![SMC Networks EXW1-BMJA Series Скачать руководство пользователя страница 44](http://html1.mh-extra.com/html/smc-networks/exw1-bmja-series/exw1-bmja-series_operation-manual_1299837044.webp)
-44-
No.EX
※※
-OMZ0016
(8) Protocol
Sets the wireless communication protocol.
* To pair with an EX600-W series unit, V.1.0 must be set.
This also applies when building a wireless system consisting of both EXW1 and EX600-W series.
•V.1.0: The same wireless communication method as EX600-W is used, and the [Frequency channel
select function (F.C.S.)] is unavailable. The communication speed is 250 kbps.
•V.2.0: This can be applied to a wireless system consisting solely of EXW1 series units.
The [Individual setting of Output while upper communication is not established] and [Frequency
channel select function (F.C.S.)] are available. The communication speed is 1 Mbps.
See the table of combinations provided below.
Combination
*4
Applicable function
Wireless
Base
Wireless
Remote
Communication
distance
Protocol
Frequency
channel
select function
(F.C.S.)
Web
function
EXW1
EXW1
Up to 100 m
V.1.0/V.2.0
Available
*1
-
EXW1
EXW1+EX600
*2
V.1.0
NA
-
EXW1
EX600
Up to 10 m
V.1.0
NA
-
EX600
EXW1
Up to 10 m
V.1.0
NA
Available
*3
EX600
EXW1+EX600
Up to 10 m
V.1.0
NA
Available
*3
EX600
EX600
Up to 10 m
V.1.0
NA
Available
*1: Available in protocol V.2.0.
*2: Up to 100 m between an EXW1 series Base and Remote, and up to 10 m between an EXW1 series Base
and an EX600-W series Remote.
*3: The settings and monitor function are restricted when EX600-WEN/WPN and EXW1-R* are used in
combination.
*4: For combinations involving EX600-W series, refer to the operation manual for the product in use.
(9) Time information
The time information is the time that the product recognizes. It is used for a timestamping event and other
logs.
Until "synchronization" is performed, it displays the time elapsed since startup.
(10) Time synchronization
This sends the time information of the PC to the product and synchronizes it. If the time information of
the PC is needed for a timestamping event and other logs, perform time synchronization.
•
The protocol can be changed only when no Remote is registered in the EXW1-BMJA*.
Make changes only after unregistering any registered Remotes.
Note that an unregistration pop-up window will appear in the I/O Configurator.