# Output unit
Remote e-CON output type LED indicator
- Remote e-CON output type LED indicator specifications
LED name
Function
Color of LED
Single Operation
PWR
Indicates the power supply voltage
(US1/ US2) status
Green LED
is ON.
Normal power supply voltage for control and input
(US1) ON, and normal power supply voltage level
for output (US2)
Red LED
flashes.
Abnormal power supply voltage level for output
(US2)
(Applicable when the power supply voltage
monitor is enabled)
OFF
Power supply for control and input (US1) is not
supplied.
MS
Status of remote output
Green LED
is ON.
Operating normally
Red LED
flashes.
Restorable error is detected.
- Short-circuit detection of output load
Red LED
flashes.
Abnormal power supply voltage for control and
input (US1)
(Applicable when the power supply voltage
monitor is enabled)
Red LED is
ON
Unrestorable error is detected.
OFF
Power supply for control and input (US1) is not
supplied.
W-SS
Radio wave receiving intensity
Green LED
is ON.
Received radio wave intensity level 3
Green LED
flashes
(1Hz)
Received radio wave intensity level 2
Green LED
flashes
(2Hz)
Received radio wave intensity level 1
Red LED
flashes.
Wireless communication is not connected.
OFF
Base not registered
W-NS
Wireless communication
connection status
Green LED
is ON.
Remote output connected correctly
Red LED
flashes.
Remote output not connected
Red LED is
ON
Remote output not connected
(Non-restorable error in wireless communication)
Red/green
Wireless communication connection is being
configured (pairing)
Orange LED
is ON
Forced output mode is ON
Orange LED
flashes.
Pairing operation is in progress
OFF
Base is not connected
* If there are multiple conditions for LED ON/Flashing, the detailed information can be seen only when the setting of the diagnostic