-24-
No.EX##-OMN0011-B
Network communication specifications
Item
Specifications
Protocol EtherCAT
EtherCAT mode
Direct Mode (No MAC address)
∗
: Does not support Open Mode.
Transmission speed
100 Mbps
Transmission medium
Standard Ethernet cable (CAT5) (100BASE-TX)
Number of nodes connected
(Up to 65,535 nodes.)
Network topology
Daisy chain
Maximum segment length
Up to 100 m (328 ft)
Address setting
Manual setting is not required, automatically set
EX260-SEC1/-SEC2 32
outputs
Number of outputs
EX260-SEC3/-SEC4 16
outputs
Vendor ID
00000114 hex (276)
EX260-SEC1 01000001
hex
(16777217)
EX260-SEC2 01000002
hex
(16777218)
EX260-SEC3 01000003
hex
(16777219)
Product code
EX260-SEC4 01000004
hex
(16777220)
Connectable valve series
Valve Series
SY series
SY3000, SY5000
VQC series
VQC1000, VQC2000, VQC4000
SV series
SV1000, SV2000, SV3000 (10 type tie-rod base)
S0700 series
S0700
∗
: The valve manifolds that can be connected are the same as those connectable to EX250 series.