Safety Instructions

 

 
These safety instructions are intended to prevent hazardous situations and/or equipment damage.

 

These instructions indicate the level of potential hazard with the labels of "Caution", "Warning" or "Danger".

 

They are all important notes for safety and must be followed in addition to International Standards 
(ISO/IEC)

*1)

, and other safety regulations.

 

*1) ISO 4414: Pneumatic fluid power -- General rules relating to systems.

 

ISO 4413: Hydraulic fluid power -- General rules relating to systems.

 

IEC 60204-1: Safety of machinery -- Electrical equipment of machines .(Part 1: General requirements)

 

ISO 10218: Manipulating industrial robots -Safety.

 

etc.

 

 

Caution

 

Caution

 indicates a hazard with a low level of risk which, if not avoided, could 

result in minor or moderate injury.

 

 

Warning

 

Warning

 

indicates a hazard with a medium level of risk which, if not avoided, 

could result in death or serious injury.

 

 

Danger

 

Danger

 

indicates a hazard with a high level of risk which, if not avoided, will 

result in death or serious injury.

 

 

Warning

 

1. The compatibility of the product is the responsibility of the person who designs the 

equipment or decides its specifications.

 

Since the product specified here is used under various operating conditions, its compatibility with specific 
equipment must be decided by the person who designs the equipment or decides its specifications 
based on necessary analysis and test results. 
The expected performance and safety assurance of the equipment will be the responsibility of the 
person who has determined its compatibility with the product. 
This person should also continuously review all specifications of the product referring to its latest catalog 
information, with a view to giving due consideration to any possibility of equipment failure when 
configuring the equipment.

 

2. Only personnel with appropriate training should operate machinery and equipment.

 

The product specified here may become unsafe if handled incorrectly.

 

The assembly, operation and maintenance of machines or equipment including our products must be 
performed by an operator who is appropriately trained and experienced.

 

3. Do not service or attempt to remove product and machinery/equipment until safety is 

confirmed.

 

1. The inspection and maintenance of machinery/equipment should only be performed after measures to 

prevent falling or runaway of the driven objects have been confirmed.

 

2. When the product is to be removed, confirm that the safety measures as mentioned above are 

implemented and the power from any appropriate source is cut, and read and understand the specific 
product precautions of all relevant products carefully. 

3. Before machinery/equipment is restarted, take measures to prevent unexpected operation and malfunction.

 

4. Contact SMC beforehand and take special consideration of safety measures if the 

product is to be used in any of the following conditions.

 

1. Conditions and environments outside of the given specifications, or use outdoors or in a place 

exposed to direct sunlight. 

2. Installation on equipment in conjunction with atomic energy, railways, air navigation, space, shipping, 

vehicles, military, medical treatment, combustion and recreation, or equipment in contact with food and 
beverages, emergency stop circuits, clutch and brake circuits in press applications, safety equipment or 
other applications unsuitable for the standard specifications described in the product catalog.

 

3. An application which could have negative effects on people, property, or animals requiring special 

safety analysis.

 

4. Use in an interlock circuit, which requires the provision of double interlock for possible failure by using 

a mechanical protective function, and periodical checks to confirm proper operation. 

Содержание EX250-IE1

Страница 1: ...No EX OME0004 E PRODUCT NAME Input block MODEL Series Product Number EX250 IE1 EX250 IE2 EX250 IE3 ...

Страница 2: ... Safety Instructions 2 Model Indication and How to Order 8 Summary of Product parts 8 Mounting and Installation 9 Installation 9 Wiring 10 Internal circuit 12 Display Setting 18 Troubleshooting 19 Specifications 20 Dimensions 21 Option 22 ...

Страница 3: ... equipment failure when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly The assembly operation and maintenance of machines or equipment including our products must be performed by an operator who is appropriately trained and experienced 3 Do not service or attempt to remo...

Страница 4: ...r responsibility a replacement product or necessary parts will be provided This limited warranty applies only to our product independently and not to any other damage incurred due to the failure of the product 3 Prior to using SMC products please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products 2 Vacuum pads are excluded from this 1 ...

Страница 5: ...duct outside of the specifications Do not use for flammable or harmful fluids Fire malfunction or damage to the product can result Verify the specifications before use Do not operate in an atmosphere containing flammable or explosive gases Fire or an explosion can result This product is not designed to be explosion proof If using the product in an interlocking circuit Provide a double interlocking...

Страница 6: ...allation wiring environment adjustment operation maintenance etc described below must also be followed Product specifications The direct current power supply to combine should be UL1310 Class 2 power supply when conformity to UL is necessary The product is a UL approved product only if they have a mark on the body Use the specified voltage Otherwise failure or malfunction can result Reserve a spac...

Страница 7: ...rated into equipment Otherwise noise can cause malfunction Separate the power line for output devices from the power line for control Otherwise noise or induced surge voltage can cause malfunction Environment Select the proper type of protection according to the environment of operation IP67 protection is achieved when the following conditions are met 1 The units are connected properly with fieldb...

Страница 8: ...tion failure Please refer to the PLC manufacturer s manual etc for details of programming and addresses For the PLC protocol and programming refer to the relevant manufacturer s documentation Maintenance Turn off the power supply stop the supplied air exhaust the residual pressure and verify the release of air before performing maintenance There is a risk of unexpected malfunction Perform regular ...

Страница 9: ...ry of Product parts No Part name Function 1 Input equipment connector Connects the input equipment such as sensor etc 1 2 Operation display LED Displays the status of the power supply and input 2 1 For the wiring refer to page 10 2 For the Display Setting refer to page 18 ...

Страница 10: ...Connect end plate and tighten removed screws by specified tightening torque 0 6 Nm Exchange of input block Remove screws from end plate and release connection of each unit Replace old input block with new one Tie rod does not need to be removed Connect end plate and tighten removed screws by specified tightening torque 0 6 Nm Caution for maintenance 1 Be sure turn off power supplies 2 Be sure that...

Страница 11: ...plug 2 Tighten the lock nut on the cable side by turning it clockwise by hand 3 Confirm that the connector does not move Input connector pin layout EX250 IE1 M12 connector 5 pin Socket 1 Input No 1 is connected to the pin No 2 of the input connector 0 2 input signals can be directly inputted the input connector 0 2 NC Not connected ...

Страница 12: ...e position of the mounting key when selecting the sensor NOTE Mount a waterproof cap on each unused connector of Input block Proper use of the waterproof cap can achieve IP67 enclosure Tightening torque 0 05 Nm for M8 0 1N m for M12 For the waterproof cap refer to page 22 Correlation between input number and Input Block The total number of Input and Output blocks can not exceed 10 The maximum inpu...

Страница 13: ... 12 No EX OME0004 E Internal circuit EX250 IE1 input circuit construction 1 NPN sensor 2 PNP sensor ...

Страница 14: ... 13 No EX OME0004 E 3 Two wire sensor EX250 IE2 input circuit construction 1 NPN sensor ...

Страница 15: ... 14 No EX OME0004 E 2 PNP sensor 3 Two wire sensor ...

Страница 16: ... 15 No EX OME0004 E EX250 IE3 input circuit construction 1 NPN sensor 2 PNP sensor ...

Страница 17: ... 16 No EX OME0004 E 3 Two wire sensor ...

Страница 18: ...y the fuse cutting In this case the user must fix the cause of the short circuit before exchange the fuse In changing release the combination of units and perform by individual input block For the Mounting Removal of the input block refer to page 9 Fuse model EX9 FU05 Mounting the marker To install the marker enable the number of input to identify the signal name etc Prepare the marker by user Mar...

Страница 19: ... Logic 0 Switch setting Applicable sensor to the Input Block can be switched to NPN PNP Remove the input block then set up the switch with a sharp pointed watchmakers screw driver etc Install the input block after the setting For the Mounting Removal of the input block refer to page 9 The default switch setting of the product is PNP NOTE Be sure to disconnect the power supply before setting the sw...

Страница 20: ...reakage of input block Confirm input power 24 V of SI unit Exchange SI unit Exchange input block 0 to 3 LED Input signal ON OFF LED No lights up No lights off Countermeasures Confirm connector connecting Confirm the kind of sensors PNP NPN Confirm after reversing the sensors Exchange input block ...

Страница 21: ...sensors Current source type PNP output Current sink type NPN output 1 Rated voltage 19 2 to 28 8 VDC 2 Logic 1 input voltage VH 11 to 30 V Logic 0 input voltage VL 3 to 5 V Logic 1 input current IH 8 mA Typ Two wire sensor connection Possible Logic 0 allowable current IL Max 2 5 mA Input delay time 3 msec Typ Sensor supply current Max 120 mA input block 30 mA sensor 3 Short circuit protection Fuse...

Страница 22: ... 21 No EX OME0004 E Dimensions EX250 IE1 EX250 IE2 EX250 IE3 ...

Страница 23: ... 3 m SMC PCA 1557772 M8 3 pins cable with connector 3 m fieldwireable connector PCA 1557730 M8 3 pins plug PCA 1557743 M12 4 pins plug PCA 1557756 Waterproof cap Mounted on the unused ports of the input block The proper use of this waterproof cap can achieve IP67 enclosure NOTE Tighten the waterproof cap by the specified tightening torque 0 05 Nm for M8 0 1 Nm for M12 ...

Страница 24: ...dded E Contents are added July 2017 4 14 1 Sotokanda Chiyoda ku Tokyo 101 0021 JAPAN Tel 81 3 5207 8249 Fax 81 3 5298 5362 URL http www smcworld com Note Specifications are subject to change without prior notice and any obligation on the part of the manufacturer 2010 2017 SMC Corporation All Rights Reserved ...

Отзывы: