SMC Networks EX250-IE1 Скачать руководство пользователя страница 1

No.EX

※※

-OME0004-E 

 

 

 

 

 

 

 

 

 

 

PRODUCT NAME 

 

Input block

 

 

MODEL / Series / Product Number 

 

EX250-IE1 
EX250-IE2 
EX250-IE3

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Содержание EX250-IE1

Страница 1: ...No EX OME0004 E PRODUCT NAME Input block MODEL Series Product Number EX250 IE1 EX250 IE2 EX250 IE3 ...

Страница 2: ... Safety Instructions 2 Model Indication and How to Order 8 Summary of Product parts 8 Mounting and Installation 9 Installation 9 Wiring 10 Internal circuit 12 Display Setting 18 Troubleshooting 19 Specifications 20 Dimensions 21 Option 22 ...

Страница 3: ... equipment failure when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly The assembly operation and maintenance of machines or equipment including our products must be performed by an operator who is appropriately trained and experienced 3 Do not service or attempt to remo...

Страница 4: ...r responsibility a replacement product or necessary parts will be provided This limited warranty applies only to our product independently and not to any other damage incurred due to the failure of the product 3 Prior to using SMC products please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products 2 Vacuum pads are excluded from this 1 ...

Страница 5: ...duct outside of the specifications Do not use for flammable or harmful fluids Fire malfunction or damage to the product can result Verify the specifications before use Do not operate in an atmosphere containing flammable or explosive gases Fire or an explosion can result This product is not designed to be explosion proof If using the product in an interlocking circuit Provide a double interlocking...

Страница 6: ...allation wiring environment adjustment operation maintenance etc described below must also be followed Product specifications The direct current power supply to combine should be UL1310 Class 2 power supply when conformity to UL is necessary The product is a UL approved product only if they have a mark on the body Use the specified voltage Otherwise failure or malfunction can result Reserve a spac...

Страница 7: ...rated into equipment Otherwise noise can cause malfunction Separate the power line for output devices from the power line for control Otherwise noise or induced surge voltage can cause malfunction Environment Select the proper type of protection according to the environment of operation IP67 protection is achieved when the following conditions are met 1 The units are connected properly with fieldb...

Страница 8: ...tion failure Please refer to the PLC manufacturer s manual etc for details of programming and addresses For the PLC protocol and programming refer to the relevant manufacturer s documentation Maintenance Turn off the power supply stop the supplied air exhaust the residual pressure and verify the release of air before performing maintenance There is a risk of unexpected malfunction Perform regular ...

Страница 9: ...ry of Product parts No Part name Function 1 Input equipment connector Connects the input equipment such as sensor etc 1 2 Operation display LED Displays the status of the power supply and input 2 1 For the wiring refer to page 10 2 For the Display Setting refer to page 18 ...

Страница 10: ...Connect end plate and tighten removed screws by specified tightening torque 0 6 Nm Exchange of input block Remove screws from end plate and release connection of each unit Replace old input block with new one Tie rod does not need to be removed Connect end plate and tighten removed screws by specified tightening torque 0 6 Nm Caution for maintenance 1 Be sure turn off power supplies 2 Be sure that...

Страница 11: ...plug 2 Tighten the lock nut on the cable side by turning it clockwise by hand 3 Confirm that the connector does not move Input connector pin layout EX250 IE1 M12 connector 5 pin Socket 1 Input No 1 is connected to the pin No 2 of the input connector 0 2 input signals can be directly inputted the input connector 0 2 NC Not connected ...

Страница 12: ...e position of the mounting key when selecting the sensor NOTE Mount a waterproof cap on each unused connector of Input block Proper use of the waterproof cap can achieve IP67 enclosure Tightening torque 0 05 Nm for M8 0 1N m for M12 For the waterproof cap refer to page 22 Correlation between input number and Input Block The total number of Input and Output blocks can not exceed 10 The maximum inpu...

Страница 13: ... 12 No EX OME0004 E Internal circuit EX250 IE1 input circuit construction 1 NPN sensor 2 PNP sensor ...

Страница 14: ... 13 No EX OME0004 E 3 Two wire sensor EX250 IE2 input circuit construction 1 NPN sensor ...

Страница 15: ... 14 No EX OME0004 E 2 PNP sensor 3 Two wire sensor ...

Страница 16: ... 15 No EX OME0004 E EX250 IE3 input circuit construction 1 NPN sensor 2 PNP sensor ...

Страница 17: ... 16 No EX OME0004 E 3 Two wire sensor ...

Страница 18: ...y the fuse cutting In this case the user must fix the cause of the short circuit before exchange the fuse In changing release the combination of units and perform by individual input block For the Mounting Removal of the input block refer to page 9 Fuse model EX9 FU05 Mounting the marker To install the marker enable the number of input to identify the signal name etc Prepare the marker by user Mar...

Страница 19: ... Logic 0 Switch setting Applicable sensor to the Input Block can be switched to NPN PNP Remove the input block then set up the switch with a sharp pointed watchmakers screw driver etc Install the input block after the setting For the Mounting Removal of the input block refer to page 9 The default switch setting of the product is PNP NOTE Be sure to disconnect the power supply before setting the sw...

Страница 20: ...reakage of input block Confirm input power 24 V of SI unit Exchange SI unit Exchange input block 0 to 3 LED Input signal ON OFF LED No lights up No lights off Countermeasures Confirm connector connecting Confirm the kind of sensors PNP NPN Confirm after reversing the sensors Exchange input block ...

Страница 21: ...sensors Current source type PNP output Current sink type NPN output 1 Rated voltage 19 2 to 28 8 VDC 2 Logic 1 input voltage VH 11 to 30 V Logic 0 input voltage VL 3 to 5 V Logic 1 input current IH 8 mA Typ Two wire sensor connection Possible Logic 0 allowable current IL Max 2 5 mA Input delay time 3 msec Typ Sensor supply current Max 120 mA input block 30 mA sensor 3 Short circuit protection Fuse...

Страница 22: ... 21 No EX OME0004 E Dimensions EX250 IE1 EX250 IE2 EX250 IE3 ...

Страница 23: ... 3 m SMC PCA 1557772 M8 3 pins cable with connector 3 m fieldwireable connector PCA 1557730 M8 3 pins plug PCA 1557743 M12 4 pins plug PCA 1557756 Waterproof cap Mounted on the unused ports of the input block The proper use of this waterproof cap can achieve IP67 enclosure NOTE Tighten the waterproof cap by the specified tightening torque 0 05 Nm for M8 0 1 Nm for M12 ...

Страница 24: ...dded E Contents are added July 2017 4 14 1 Sotokanda Chiyoda ku Tokyo 101 0021 JAPAN Tel 81 3 5207 8249 Fax 81 3 5298 5362 URL http www smcworld com Note Specifications are subject to change without prior notice and any obligation on the part of the manufacturer 2010 2017 SMC Corporation All Rights Reserved ...