Page: 10
3.5 MODULE ADDRESS SWITCH
For digital interface applications the module address switch (or Modbus node) must be set per Table 3-2:
P
OSITION
A
DDRESS
P
OSITION
A
DDRESS
1
Sensor 1
9
Sensor 09
2
Sensor 2
A
Sensor 10
3
Sensor 3
B
Sensor 11
4
Sensor 4
C
Sensor 12
5
Sensor 5
D
Sensor 13
6
Sensor 6
E
Sensor 14
7
Sensor 7
F
Sensor 15
8 Sensor
8 0 Software
Menu
Table 3-2
Sensor Module Address Switch Positions
N
OTE
For Sentry applications only sensor addresses 1-8 are allowed. If using Modbus output sensor
addresses 1-15 are available. Position 0 allows the Modbus Address to be set by software
menu, in the range 16-254.
Figure 3-1
Transmitter Face Plate