Operation and Maintenance Manual
– SCD Smoke Dampers
Version 1
Date 04 2018
Page 67 of 81
Maintenance
At least once a year carry out the following maintenance and inspection activities:
•
Clean the rain detector with a damp cloth, possibly with a mild cleaning agent. (Do
not scour the detector surface)
•
Check the wind detector functioning for free turning of the
•
fan
•
Check the operation of detectors (wind and rain simulation)
•
Check if all smoke extraction and ventilation systems are connected properly
In regard to the weather control panel, this Operation and Maintenance Manual
contains only basic technical data and information about installation, start-up, maintenance
and close-down. Both the Installer and the User are required to know and apply the
complete version of the “Installation and Operation Manual”, which is provided along with
the control panel.
6.2.
ACCESSORIES OF THE WEATHER STATION
RS 2d
A heated rain detector (the heater is activated
after the detector response, and deactivated
after drying),
about 80
cm² sensor area
With a fixing console.
WM 1
An anemometer (cup type, rotational) for
measuring the wind velocity.
RS 2d-WM 1
A combination of RS 2d and WM 1 detectors
described above, installed according to the
mounting angle