E-xxx-230 actuator
Rys. 35. E300-230 actuator.
Technical Data:
Supply voltage:
230 V~, 50 Hz,
Current consumption
100 mA,
Feed force:
500 N when feeding, 250 N when pulling,
Feed speed
ca. 10 mm/s,
Operating mode (EN 60034)
S3 25%,
Ingress
Protection
Rating
(EN 60529):
IP 54 (300 mm outreach), IP 33 (500 mm outreach),
Ambient temperature:
-100C to +600C
Power cable:
3 x 1.5 mm
2
,
Load capacity:
230 V~ / 1 A
The actuator is equipped with an overload circuit breaker. After the circuit breaker
has been triggered, it is necessary to move the actuator back (start it in the opposite
direction) before it can be restarted in the same direction as the limit switch triggered.
Assembly recommendations for E-xxx-24, E-xxx-230 actuators:
•
Observe relevant OSH regulations, directives and commonly accepted technical
practices. This type of actuators may be connected to control panels provided by
Smay Sp. z o.o. When using the actuators with other panels, pay attention to
compatibility.
•
The actuators may only be connected to mains characterized with parameters
(voltage and current) compatible with the ones given on the device housing.
•
Actions performed on live device elements should be taken only by authorized
personnel only. Disconnect the actuator from power supply and secure it against
reconnection when performing such actions.
•
The actuator should be connected to the connection box located in the mounting
location. When selecting the location of the connection box, take into account the
actuator movement (leaning) during operation.
•
The connection box should be protected against tearing the cable out.
•
The actuator may only be used when installed at the height greater than 2.5 m.