background image

>>

 Operating & installation instructions bravour 

Subject to technical changes. 

V 2.1.5

 

 

 

 

www.SmartHeat.de 

>> 

21 

Water analysis and water treatment 

Planners and installers must check on the system if the available feed water is appropriate to fill the heating system with 
regard to the total hardness according to VDI 2035 sheet 1. The result of this test must be transmitted in writing to the 
builder / operator. The decisive factors are the heating performance and the specific system volume: 

  

Regarding this treatment the VDI 2035 gives three options: 
  

 

Softening / demineralisation  

 

Hardness stabilisation  

 

Hardness precipitation  

 
At this, the 

softening

 represents the preferred procedure to avoid stone formation, at which the alkaline earths (mag-

nesium  and  calcium  ions)  are  permanently  removed  from  the  system.  However,  hereby  sodium  hydrogen  carbonate 
(NaHCO

3

) is formed in the system, which converts to alkalinized sodium carbonate (Na

2

CO

3

) by heating up the heating 

water. Since the generated CO

2

 escapes from the system at the same time, the pH value demanded in the VDI 2035 

sheet 2 between 8.2 and 9.5 (when using aluminium maximum 8.5) may considerably be exceeded. However, if the ph 
value is exceeded, there is a risk of corrosion damages, so that it is necessary to counteract such damages in a second 
step. 
  
In the 

hardness stabilisation

 additives are added to the heating water by which the lime deposits in the system are influ-

enced in a way that formation of stone is being avoided. Contrary to the softening the stone formers are not removed 
from the system. Regarding the selection, dosing, monitoring and disposal of the additives and of the conditioned heat-
ing water it is necessary to take additional measures. It is necessary to make sure that the additives themselves as well 
as combined with other products which need to be used do not cause any corrosion damages. Furthermore, no prod-
ucts containing phosphates  should be used for hardness  stabilisation since they precipitate as calcium phosphate mud 
together with lime. 
 
In the frame of the 

hardness precipitation

 substances are added to the heating water, which let the dissolved alkaline 

earths  precipitate  as  mud.  This  mud  must  be  removed  from  the  heating  system  by  system  technical  and  operational 
measures (desludging). 

Total heat output   

Total hardness  

Total hardness  

Total hardness  

In kW 

In  °dH  at  <20l/kW  least 
boiler screen surface 

In °dH at >20l/kW<50l/kW 
least boiler screen surface 

In  °dH  >50l/kW  least 
boiler screen surface 

<50kW 

No requirements or   

11.2°dH 

0.11°dH 

<16.8°dH 

>50kW<200kW 

11.2°dH 

8.4°dH 

0.11°dH 

Содержание bravour 008 BWi

Страница 1: ...t to technical changes Operating installation instructions bravour www SmartHeat de 0 O Op pe er ra at ti in ng g i in ns st ta al ll la at ti io on n i in ns st tr ru uc ct ti io on ns s compact heat...

Страница 2: ...ptimization according to ecological points of view The increasing performance as well as the use of coolants which are very harmful to the environment are to important criteria which had been taken in...

Страница 3: ...embly_______________________________________________________________________________ 15 8 1 Connection at the side of the heat source _______________________________________________________ 15 8 2 Con...

Страница 4: ...relevant VDE EN and IEC standards must be complied with for electrical connection of heat pumps The local connecting conditions of the utilities must be observed The operator must in particular make s...

Страница 5: ...thin the usage frequency refer to the data sheet in Germany 50Hz In emergency situations decommission the heat pump resp switch in currentless condition main and control voltage Only expert approved s...

Страница 6: ...uicker effective at the ground collector evaporator and the energy supply is made available as usable energy by the heat pump The heat emitting side of the SmartHeat bravour heat pump operates with a...

Страница 7: ...50 100 100 o Carbon dioxide in ppm 5 5 10 10 5 5 10 10 o Ratio HCO3 SO4 2 1 1 Nitrate in ppm 100 100 Oxygen in ppm 1 1 8 8 1 1 8 8 o Ammonia in ppm 2 2 10 10 2 2 10 10 o Solute iron in ppm 0 2 0 2 0 5...

Страница 8: ...pump device during production at the factory The indications for the following heat pumps are binding bravour serie BW i WW i The bravour module active cooling represents a firmly combined unit togeth...

Страница 9: ...of the heat pump this gives a very reasonable possibility regarding energy consumption for cooling Application areas The module for externally internal passive cooling is based on a plate heat exchan...

Страница 10: ...heat pump basic device A separate supply is not necessary Hydraulic connection There are no differences to the classic heat pump series without cooling module regarding the hydraulic connection of th...

Страница 11: ...rmal and raise to a higher temperature level The terminals provided are in the chapter 8 3 Connection of the domestic hot water tank Proper use The module solar is an optional module for the upgrading...

Страница 12: ...t de 11 5 Device view Fig perspective view Fig isometric view open Fig front view Fig side view right Deaerator Inverter Tank Control unit Operating unit Connection opening domestic water Refrigeratio...

Страница 13: ...ect to technical changes Operating installation instructions bravour www SmartHeat de 12 Fig lower side plate right Fig Upper side plate right and left Fig rear plate Source inlet Source outlet Heat s...

Страница 14: ...y perform commissioning and maintenance works and en sure free working space on all sides refer to the recommended minimum clearances The installation space must be dry and frost free and have a plane...

Страница 15: ...ions bravour www SmartHeat de 14 Minimum clearances for the installation Fig Minimum dimensions for the installation of bravour Foundation Fig Foundation plan bravour 100cm 100cm 25cm 120cm Observe th...

Страница 16: ...r to attain the values indicated on the data sheets resp in order to avoid malfunctions Compared to traditional incinerators of higher mass flows i e larger pipe cross sections and corresponding pump...

Страница 17: ...in a complete failure of the heat pump After having performed the installation of the heating system fill bleed and squeeze off the heating system For the optimum connection comprehensive hydraulic a...

Страница 18: ...g pressure 10 bar Operating temperature 90 C Heating buffer tank Material S 235 JR Operating pressure 3 bar Operating temperature 110 C Content domestic water 193 litre Content heating water 56 litre...

Страница 19: ...cument the earth conductor resistance and the isolation resistance according to DIN VDE 0701 and DIN VDE 0702 These tests must be repeated according to the intervals applicable on site or according to...

Страница 20: ...3 N PE 50Hz 400V Inverter 230 V 1 x supply heat pump 1 N PE 50Hz 230V 1 x supply control voltage 1 N PE 50Hz 230V 1 x heating coil 3 N PE 50Hz 400V or 1 N PE 50Hz 230V Flow monitor source The flow of...

Страница 21: ...are cases in the heat pump itself Wrong settings on the controller may have similar effects The triggering of corresponding sensors and the signalling of a mal function serve to protect the system and...

Страница 22: ...xceeded there is a risk of corrosion damages so that it is necessary to counteract such damages in a second step In the hardness stabilisation additives are added to the heating water by which the lim...

Страница 23: ...roller instructions refer to part 2 of the operating instructions Furthermore you obtain information regarding the setting of the required room and hot water temperatures the setting of your own daily...

Страница 24: ...necessary to have the system cleaned by an install er At this the condenser should be flushed contrary to the direction of flow In order to avoid that soiled heating water attains the heating system...

Страница 25: ...of 10 kW in order to guarantee the required hot water preparation Of course there are sufficient reserves for the dry heating phase Expect to spend more money in electricity costs during the first he...

Страница 26: ...it use flexible tubes for connection Freezing protection of the heat pump and the connection tubes should be ensured by the installer and user A minimum outgoing and backflow temperature of 25 C has t...

Страница 27: ...V2 1 5 Subject to technical changes Operating installation instructions bravour www SmartHeat de 26 Hydraulic system bravour BW i...

Страница 28: ...Operating installation instructions bravour Subject to technical changes V 2 1 5 www SmartHeat de 27 Hydraulic system bravour WW i...

Страница 29: ...V2 1 5 Subject to technical changes Operating installation instructions bravour www SmartHeat de 28 Hydraulic system bravour DI...

Страница 30: ...infold S 1 2 Four way brine circuit mainfold S 1 3 Five way brine circuit mainfold S 1 4 Six way brine circuit mainfold S 2 Safety set source S 5 Set natural cooling S 6 Safety assembly source H1 Safe...

Страница 31: ...V2 1 5 Subject to technical changes Operating installation instructions bravour www SmartHeat de 30...

Страница 32: ...Operating installation instructions bravour Subject to technical changes V 2 1 5 www SmartHeat de 31 15 Appendix EU declaration of conformity Technical data Terminal assignment plan...

Страница 33: ......

Страница 34: ...WWi R bravour 008 BWi N bravour 012 BWi N Richtlinien directives 2014 68 EU Druckger terichtlinie pressure equipment directive 2014 35 EU Niederspannungsrichtlinie Low voltage directive 2014 30 EU EM...

Отзывы: