HRC200 Industrial Remote Control User Manual Page 13 of 16
No.
Item
Range
Default
Description
2: Even Parity
4
Stop Bit
(0-1)
0
0: 1-bit
1: 2-bit
5
Aux. Input 1
(0-9)
1
0: Not Used
1: Remote Control Inhibit
2: Simulate Start Key
3: Simulate Stop Key
4: Simulate Unload Key
5: Simulate Load Key
6: Simulate F1 Key
7: Simulate F2 Key
8: Simulate Running Status
9: Simulate Alarm Status
6
Aux. Input 2
(0-9)
0
7
Aux. Output 1
(0-6)
5
0: Not Used
1: Start Control
2: Stop Control
3: Unload Control
4: Load Control
5: F1 Control
6: F2 Control
8
Aux. Output 2
(0-6)
6
9
Aux. Output 3
(0-6)
0
10
Aux. Output 4
(0-6)
0
11
Aux. Output 5
(0-6)
0
12
Aux. Output 1
Output Delay
(0-999.9)s
1.0s
When it is set as 0, relay
continuously outputs when the
remote control key is firstly
pressed, relay stops output when
the key is pressed again.
When it is set as other values,
relay disconnects output after
outputting set delay value.
13
Aux. Output 2
Output Delay
(0-999.9)s
1.0s
14
Aux. Output 3
Output Delay
(0-999.9)s
1.0s
15
Aux. Output 4
Output Delay
(0-999.9)s
1.0s
16
Aux. Output 5
Output Delay
(0-999.9)s
1.0s
6
SYSTEM APPLICATION DIAGRAM
Remote control communicates with receiver via LoRa, engine controller and receiver can be
controlled by RS485 communication or digital input/output port.
Fig.7 HRC200 System Application Diagram