No.
Function
Cable
Note
22
IN
23
C/B
-
1.0mm
2
Main switch close input, active when it is short
circuit.
24
IN
25
L1
1.0mm
2
AC input.
26
27
L2
1.0mm
2
28
29
L3
1.0mm
2
30
S1
CT A Phase Input
2.5mm
2
Externally connected to secondary coil of current
transformer (rated 5A).
31
S2
32
S1
CT C Phase Input
2.5mm
2
Externally connected to secondary coil of current
transformer (rated 5A).
33
S2
34
P>80% Output
Normally
Open
2.5mm
2
Output when P>80%Pn and
delay is over.
Normally open, N/C
contactor; Volts free
output; 7A Rated
35
COM
36
Normally
Close
37
P<20% Output
Normally
Open
2.5mm
2
Output when P<20%Pn and
delay is over.
Normally open, N/C
contactor; Volts free
output; 7A Rated
38
COM
39
Normally
Close
40
Low Power
Output
Normally
Open
2.5mm
2
Output when P<10%Pn (it
can be set to P<5%Pn or
other value) and delay is
over.
Normally open, N/C
contactor; Volts free
output; 7A Rated
41
COM
42
Normally
Close
43
INCR.
2.5mm
2
Raise speed.
Normally open, Volt
free, 7A Rated.
44
45
DECR.
2.5mm
2
Reduce speed.
Normally open, Volt
free, 7A Rated.
46
47
Hz Selection
-
1.0mm
2
50/60Hz to choose
Short circuit is
60Hz
48
IN
LINK Used for parameter setting or software upgrade.