HLS300 Power Share Module User Manual
HLS300 Power Share Module Version 1.4 2019-05-16 Page 5 of 14
1
OVERVIEW
HLS300 Power Share Module
is a special design for genset power share. On the basis of the set
parameters, the module conducts automatically power share in genset running process.
The main function of HLS300 module is to share active load to each operating genset according to
genset capacitance. The module is brief to operate, easy to install and widely used for ship genset and
land genset.
2
PERFORMANCE AND CHARACTERISTICS
Main characters are as below:
Suitable for 3-phase 3-wire, single phase 2-wire systems with frequency 50/60/Hz;
Adjustable potentiometer allows for setting main parameters of power share.
Module parameters can be set via upper computer test software. LINK port should be connected to
upper computer via SG72 module (USB to LINK)
8 relay outputs, 2 of which are used for controlling INCR. speed raise, and DECR. reduce, 5 are used
for -P, UNLOADING, P>80%, P<20%, LOW-P output, and 1 is used for C/B OPEN;
1 FIXLOAD mode, 1 UNL, 1 close and 1 60Hz optional digital input;
One test button for testing relay output and panel indicators;
Wide power supply range DC(8~35)V;
35mm guide rail mounting;
Modular design, pluggable terminal, compact structure with easy installation.
3
SPECIFICATION
Table 3
– Product Parameters
Parameter
Details
Working Voltage
DC8.0V to 35.0V continuous
Overall Consumption
≤2W(Standby mode≤0.5W)
AC Input
AC50V~ AC620 V (ph-ph)
AC Frequency
50Hz/60Hz
Relay Output
7A
AC250V Volt free output
Case Dimensions
161.6mm x 89.7mm x 60.7mm
CT Secondary Current
Rated: 5A
Working Conditions
Temperature: (-25~+70)°C
Humidity: (20~95)%
Storage Conditions
Temperature: (-25~+70)°C
Insulation Intensity
Apply AC2.2kV voltage between high voltage terminal and low voltage
terminal; The leakage current is not more than 3mA within 1min.
Weight
0.45kg