HGM9560 BUS TIE MAINS PARALLEL UNIT
HGM9560 Bus Tie Mains Parallel Unit ISSUE 2013-12-30 Version 1.0 Page 29 of 51
No.
Items
Parameters
Defaults
Description
Flexible Input Ports
Flexible Input Port 1
1
Contents Setting
(0~50)
31
Remote start (demand). See form 3
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
Flexible Input Port 2
1
Contents Setting
(0~50)
0
User defined. See form 3
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
3
Arming
(0~2)
2
0: From paralleling
1: Always 2:Never
4
Active Actions
(0~3)
3
0: Warn; 1:Trip and stop 2:Trip
3: Indication
5
Active Delay
(0~20.0)s
2.0
Time from detecting active to confirm
6
Description
LCD display detailed contents when the
input is active.
Flexible Input Port 3
1
Contents Setting
(0~50)
0
User defined. See form 3
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
3
Arming
(0~2)
2
0: From paralleling 1: Always 2:Never
4
Active Actions
(0~3)
3
0: Warn; 1:Trip and stop 2:Trip
3: Indication
5
Active Delay
(0~20.0)s
2.0
Time from detecting active to confirm
6
Description
LCD display detailed contents when the
input is active.
Flexible Input Port 4
1
Contents Setting
(0~50)
13
Bus Closed. See form 3
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
Flexible Input Port 5
1
Contents Setting
(0~50)
0
User defined. See form 3
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
3
Arming
(0~2)
2
0: From paralleling 1: Always 2:Never
4
Active Actions
(0~3)
3
0: Warn; 1:Trip and stop 2:Trip
3: Indication
5
Active Delay
(0~20.0)s
2.0
Time from detecting active to confirm
6
Description
LCD display detailed contents when the
input is active.
Flexible Input Port 6
1
Contents Setting
(0~50)
0
User defined. See form 3
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
3
Arming
(0~2)
2
0: From paralleling 1: Always 2:Never
4
Active Actions
(0~3)
3
0: Warn; 1:Trip and stop 2:Trip