HGM6100N Series Genset Controller User Manual Page 32 of 47
9
SENSOR SETTING
—
When choosing sensor, standard value of sensor curve will be needed. If temperature sensor is set
as SGH (120ºC resistor type), sensor curve should be SGH (120ºC resistor type); If it is set as SGD
(120ºC resistor type), sensor curve should be SGD curve.
—
If there is difference between standard sensor curve and chosen sensor curve, select “defined
sensor”, and then input defined sensor curve.
—
When sensor curve is inputted, X value (resistance) must be in accordance with the order of higher
to lower, otherwise errors will occur.
—
When sensor is selected as “Not used”, temperature, pressure and fuel level will be display as “- -
-“ in LCD.
—
If there is no pressure sensor, but only has low pressure alarm switch, then you must set pressure
sensor as “Not used”, otherwise oil pressure low alarm shutdown may appear.
—
Can set several points of forehand or backmost as the same ordinate, as the following picture:
Fig.4 – Sensor Curve Diagram
Table 12 – Conventional Pressure Unit Conversion Table
1N/m
2
(pa)
1kgf/cm
2
1bar
(1b/in
2
) psi
1Pa
1
1.02x10
-
5
1x10
-
5
1.45x10
-
4
1kgf/cm
2
9.8x10
4
1
0.98
14.2
1bar
1x10
5
1.02
1
14.5
1psi
6.89x10
3
7.03x10
-
2
6.89x10
-
2
1