HGM6100N Series Genset Controller User Manual Page 24 of 47
No.
Items
Range
Default
Description
90(85)
86(81)
Manual Mode ATS
(0-1)
0
0: Key Switch; 1: Auto Switch.
91(86)
87(82)
Speed Raise Pulse
(0-20.0)s
0.2
It is the speed-up pulse output time, when the
unit enters the high-speed warm-up.
92(87)
88(83)
Speed Drop Pulse
(0-20.0)s
0.2
It is the speed-drop pulse output time, when
the unit enters the stop idling.
93(88)
89(84)
Fuel
Level
Low
Shutdown
(0-100)%
5
When fuel level of external level sensor falls
below the setting limit and lasts for 5s, low
fuel shutdown alarm will be initiated; if limit
value set as 0, low fuel shutdown alarm will
not be initiated.
94(89)
90(85)
ATS Open Time
(1.0-60.0)s
3.0
95(90)
91(86)
Gen PT Ratio
(0-1)
0
0: Disabled; 1: Enabled. PT primary and PT
secondary can be set.
96(91)
92(87)
Mains PT Ratio
(0-1)
0
0: Disabled; 1: Enabled. PT primary and PT
secondary can be set. HGM6110N is reserved
and without this settings.
97(91)
93(88)
Active Power Loading
Percentage
(0-1)
0
0: Disabled; 1: Enabled. When it is enabled, it
is active power/rated power*100; when it is
disabled, it 3-phase average current/rated
current*100;
98(92)
Charger
Voltage
Sampling
(0-1)
0
0: Controller; 1: ECU.
99(93) Speed Sampling
(0-1)
1
0: Controller; 1: ECU.
100(94) Temp. Sampling
(0-1)
1
0: Controller; 1: ECU.
101(95) OP Sampling
(0-1)
1
0: Controller; 1: ECU.
102(96) CAN Baud Rate
(0-1)
0
0: 250kbps; 1: 500kbps.
103(97) Rated Speed
(0-6000)r/min 1500
Rated
speed
TSC1
message sending.
Engine type: 44
GTSC1 PLUS.
104(98) Rate Idle Speed
(0-6000)r/min
750
Rate idle speed of TSC1
message sending.
105(99) ECU Comm. Address
(0-255)
3
Communication address
of
TSC1
message
sending ID.
NOTE1:
The value in first line of “Number” column is for HGM6120CAN and the value in brackets is for
HGM6110CAN; If the HGM6100N and HGM6100CAN parameter numbers are inconsistent, the second line of “Number”
column is for HGM6120N, and the value in brackets is for HGM6110N.
NOTE2:
If select high temperature inhibit, or set programmable input as High Temperature Inhibit (this input is
active), when temperature is higher than pre-setting threshold, controller sends warning signal only and not shutdown.
NOTE3:
If select low oil pressure inhibit, or set programmable input as Low Oil Pressure Inhibit (this input is active),
when low oil pressure is lower than pre-setting threshold, controller sends warning signal only and not shutdown.
NOTE4:
If default password (0318) isn’t changed, it doesn’t need to input when configuring parameters via PC
software; if the password is changed for the first time via PC software, it need to input password in password window.