HGM150 Generator Control Module
HGM150 Control Module ISSUE 2011-12-22 Version 1.3 Page 5 of 9
Item
Contents
Case Dimensions
84mm x72mm x 35mm
Panel Cutout
78mm x 66mm
Operation Condition
Temperature: (-30~+70)ºC
Humidity: (20~90)%
Storage Condition
Temperature
:
(-40~+80)ºC
Protection Level
IP55: when waterproof rubber gasket added
between controller and its panel.
IP42: when waterproof rubber gasket not added
between controller and its panel.
Insulation Intensity
Object: among input/output/power
Quote standard: IEC688-1992
Test way: AC1.5kV/1m 3mA leakage current
Weight
0.2kg
4 PANEL OPERATION
◎
Lamp test (
): press this key at least 1 second, all the indicators in the
panel will illuminate. It will test whether the indication lights are normal or
not.
◎
Alarm reset (
): when module had failure and alarm, press this key to
reset the alarm.
◎
Parameter configuration (
): can be used for setting over speed
threshold of generator. Setting procedures are as following:
1) Disconnect the module power (B+), press
key and hold, then turn on