background image

 

HGM150 Generator Control Module 

HGM150 Control Module          ISSUE 2011-12-22          Version 1.3            Page 5 of 9 

Item   

Contents   

Case Dimensions 

84mm x72mm x 35mm 

Panel Cutout 

78mm x 66mm 

Operation Condition 

Temperature: (-30~+70)ºC

 

Humidity: (20~90)% 

Storage Condition 

Temperature

(-40~+80)ºC 

Protection Level 

IP55:  when  waterproof  rubber  gasket  added 

between controller and its panel. 

IP42: when waterproof rubber gasket not added 

between controller and its panel. 

Insulation Intensity 

Object: among input/output/power 

Quote standard: IEC688-1992 

Test way: AC1.5kV/1m    3mA leakage current 

Weight   

0.2kg 

4 PANEL OPERATION   

 

◎ 

Lamp test (

): press this key at least 1 second, all the indicators in the 

panel will illuminate. It will test whether the indication lights are normal or 

not. 

◎ 

Alarm reset (

): when module had failure and alarm, press this key to 

reset the alarm. 

◎ 

Parameter  configuration  (

):  can  be  used  for  setting  over  speed 

threshold of generator. Setting procedures are as following: 

1)  Disconnect the module power (B+), press

key and hold, then turn on 

Содержание HGM150

Страница 1: ...HGM150 Genset Control Module USER MANUAL Smartgen Technology ...

Страница 2: ...ng in any medium by electronic means or other without the written permission of the copyright holder Applications for the copyright holder s written permission to reproduce any part of this publication should be addressed to Smartgen Technology at the address above Any reference to trademarked product names used within this publication is owned by their respective companies Smartgen Technology res...

Страница 3: ...1 3 Page 3 of 9 CONTENTS 1 SUMMARY 4 2 PERFORMANCE AND CHARACTERISTICS 4 3 SPECIFICATION 4 4 PANEL OPERATION 5 5 TERMINALS FUNCTION 6 6 TYPICAL APPLICATION 7 7 CASE DIMENSIONS Panel Cutout 78 mm 66mm 8 8 HGM170RE RELAY EXPANSION MODULE Optional 8 9 OVERALL DEMENIONS OF HGM170RE 9 ...

Страница 4: ...ure high water cylinder temperature over speed and external alarm protection With ETS output Crank disconnect output alarm output and over speed output LED displays all kinds of alarm states Crank disconnect and over speed are decided by generator voltage and over speed threshold can be set Built in dial switch to select frequency See the picture 3 SPECIFICATION Item Contents Working Voltage DC8 0...

Страница 5: ...ed between controller and its panel Insulation Intensity Object among input output power Quote standard IEC688 1992 Test way AC1 5kV 1m 3mA leakage current Weight 0 2kg 4 PANEL OPERATION Lamp test press this key at least 1 second all the indicators in the panel will illuminate It will test whether the indication lights are normal or not Alarm reset when module had failure and alarm press this key ...

Страница 6: ...D Terminal 2 B Connected to plant battery positive Terminal 3 ETS Output When module detects fault the output is enabled and will disconnect after 3 seconds Terminal 4 Crank Disconnect Output output when module detects output frequency more than 15Hz disconnect when less than 15Hz Terminal 5 Alarm Output When module detects fault the output is enabled and will disconnect after resetting the alarm ...

Страница 7: ...uency is 50 60Hz Terminal 11 NC Not connection Terminal 13 Over Speed Output When module detects output frequency more than pre setting over speed threshold it will output and hold after 3s delay and will disconnect after resetting the alarm or turning off the power Terminal 14 NC Not connection 6 TYPICAL APPLICATION ...

Страница 8: ... 9W 4 Auxiliary relay 30A passive output coil power 0 9W Terminals Description No Items Description Notes 1 CRANK CTRL Start relay control connect to ground HGM170RE terminals 1 CRANK CTRL 3 FUEL CTRL 9 AUX CTRL 12 STOP CTRL HGM150 terminal 3 Stop Output 4 Crank Disconnect Output 5 Alarm Output 13 Over speed Output These terminals can be arbitrarily 2 CRANK OUT Start relay output B output 3 FUEL C...

Страница 9: ...ule ISSUE 2011 12 22 Version 1 3 Page 9 of 9 11 AUX OUT2 contact normally opens interconnected to control corresponding items 12 STOP CTRL Stop relay control connect to ground 9 OVERALL DEMENIONS OF HGM170RE Note When ordering please specify 12V or 24V ...