HAT833 Series Three Power ATS Controller User Manual Page 31 of 56
No.
Item
Range
Default
Description
3
Current Monitoring
(0~1)
1
0: Disable; 1: Enable
4
CT Primary/5
(5~6000)A
500
The primary current of CT.
5
S1 Full Load Rating
(5~6000)A
500
The current of S1 taking full load
6
S2 Full Load Rating
(5~6000)A
500
The current of S2 taking full load
7
S3 Full Load Rating
(5~6000)A
500
The current of S3 taking full load
8
S1 Max kW Rating
(1~20000)kW
200
The maximum active power of S1 taking
load
9
S2 Max kW Rating
(1~20000)kW
200
The maximum active power of S2 taking
load
10
S3 Max kW Rating
(1~20000)kW
200
The maximum active power of S3 taking
load
11
Over Current Enable
(0~1)
1
0: Disable; 1: Enable
12
Over Current
(0~200)%
120
Over current set value
13
Action
(0~1)
0
0: Warn 1: Trip
14
Type
(0~1)
0
0
:
Definite Time 1
:
IDMT(Inverse Definite
MMinimum Time)
15
DMT Delay Value
(0~3600)s
10
It’s the over current delay time when
“Definite Time” is selected.
16
IDMT Delay Multiply
(1~36)
36
It’s the over current multiply when “IDMT”
is selected.
17
NEL Trip
(0~1)
0
0: Disable ; 1: Enable
18
NEL1 Set Value
(0~200)%
90
Off load output will active if the load
power has exceeded the set value and the
delay time has expired.
19
NEL1 Delay
(0~3600)s
5
20
NEL2 Set Value
(0~200)%
100
Off load output will active if the load
power has exceeded the set value and the
delay time has expired.
21
NEL2 Delay
(0~3600)s
1
22
NEL Return Enable
(0~1)
0
0: Disable ; 1: Enable
23
Set Value
(0~200)%
50
NEL control will deactivated if the load
power has fallen below the set value and
the delay time has expired.
24
Delay
(0~3600)s
5
25
NEL Num
(1~3)
3
NEL number
26
Mains Load NEL
Enable
(0~1)
0
0: Disable ; 1: Enable
Digit Inputs
1
Digital Input 1
(0~47)
1
Forced Open
2
Active Type
(0~1)
0
0: Close to activate;
1: Open to activate
3
Digital Input 2
(0~47)
8
Breaker Trip Input
4
Active Type
(0~1)
0
0: Close to activate;
1: Open to activate
5
Digital Input 3
(0~47)
0
Not Used
6
Active Type
(0~1)
0
0: Close to activate;
1: Open to activate