HAT600N Series ATS Controller User Manual 

HAT600N  Series  ATS  Controller                      Version  1.1                  2019-09-05                Page  19  of  24

 

Table 12 Functional Description of Input/Output Ports 

Pin   

Items 

Description 

Notes   

1# close output 

Volt-free relay contact output 

250V16A(relay capacity) 


2# close output 

Volt-free relay contact output 

250V16A(relay capacity) 


Aux. output 1 

NC 

Default:  ATS  power 
of L1 output. 

Volt-free  relay  contact  output: 
250V16A 

Common 

NO 

Aux. output 2 

NC 

Default:  ATS  power 
of N output. 

Volt-free  relay  contact  output: 
250V16A 

Common 

10 

NO 

11 

A1 

1# AC 3-phase 4 wire voltage input 

For  single  phase,  only  connect 
A1, N1 

12 

B1 

13 

C1 

14 

N1 

15 

A2 

2# AC 3-phase 4 wire voltage input 

For  single  phase,  only  connect 
A2, N2 

16 

B2 

17 

C2 

18 

N2 

19 

B- 

Connect battery negative 

DC negative input 

20 

B+ 

To  start  engine,  connect  the 
terminal to battery positive   

DC 

positive 

input 

(8-35)V 

controller power supply 

21 

1# close input 

Detection  of  1#  switch  closing 
state, voltage free contact input 

connect GND 

22 

2# close input 

Detection  of  2#  switch  closing 
state, voltage free contact input 

connect GND 

23 

Aux. input 1 

connect GND 

 

24 

Aux. input 2 

 

25 

Aux. input 3 

 

26 

Aux. input 4 

 

27 

Aux. output 3 

Voltage free relay contact output 

250V7A 

28 
29 

Aux. output 4 

Voltage free relay contact output 

250V7A 

30 
31 

Aux. output 5 

Voltage free relay contact output 

250V7A 

32 
33 

RS485 A+ 

RS485 communication port 

 

34 

RS485 B- 

35 

RS485 GND 

36 

IA Input 

Sensing  from  Secondary  phase  A 
current 

Only 

suitable 

for 

HAT600NI/HAT600NBI 

37 

IA Output 

38 

IB Input 

Sensing  from  Secondary  phase  B 
current 

39 

IB Output 

40 

IC Input 

Sensing  from  Secondary  phase  C 
current join 

41 

IC Output 

LCD 

Contrast 

LCD Display   

Adjust the LCD contrast   

 

LINK 

Programming port 

Factory update 

 

 
 
 
 
 
 
 
 

Содержание HAT600N Series

Страница 1: ...HAT600N SERIES HAT600N HAT600NI HAT600NB HAT600NBI ATS CONTROLLER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD...

Страница 2: ...ing or storing in any medium by electronic means or other without the written permission of the copyright holder Applications for the copyright holder s written permission to reproduce any part of thi...

Страница 3: ...TION 5 4 OPERATING 6 5 LCD DISPLAY 7 6 COMMISSIONING 9 7 PARAMETERS CONFIGURATION 10 8 EVENT LOG 14 9 TIMING START 15 10 DATE AND TIME SETTING 15 11 LANGUAGE SETTING 15 12 CONTROLLER INFORMATION 16 13...

Страница 4: ...cy F2 4 Measure and display load active power apparent power power factor and 3 phase current 5 Over current alarm function 6 Over under voltage loss of phase reverse phase sequence over under frequen...

Страница 5: ...3P4W L L 80 625 V 80 480 V 3P3W L L 80 625 V Not used 1P2W L N 50 360 V 50 280 V 2P3W A B 80 625 V 80 480 V Rated Frequency 50 60Hz Close Open Trip Relay Output 16A AC250V Free Voltage relay output Pr...

Страница 6: ...off 1 or 2 power to off load 2 Close In Manual mode switch on 2 power to load Manual Press and controller enters into Manual mode Automatic Press and controller enters into AUTO mode Test Pressing thi...

Страница 7: ...Type Description 1 1 Gens Alarm Alarm When 1 genset occur failure this will display 2 1 Fail to Close Alarm When 1 breaker occur closing failure this will display 3 1 Fail to Open Alarm When 1 breake...

Страница 8: ...hase sequence is not A B C 10 2 Volt Normal Indication 2 source voltage is within the setting range Table 7 Display Status of Other Items upper to lower No Item Type Description 1 Trip alarm Alarm Tri...

Страница 9: ...s normal or not STOP TO TEST The start generator signal will turn off after pressing this key immediately CYCLE START When this mode is active generator start signal will cyclic output according to ma...

Страница 10: ...l to voltage abnormal 03 2 Normal Delay 0 9999 s 10 It is the delay of 2 power from voltage abnormal to voltage normal 04 2 Abnormal Delay 0 9999 s 5 It is the delay of 2 power from voltage normal to...

Страница 11: ...23 Under Frequency Return 0 0 75 0 Hz 48 0 Normal return value of over frequency 24 CT Ratio 5 65000 5 500 Current Transformer ratio 25 Rated Load Current 5 6000 A 500 Load rated current 26 Over Curre...

Страница 12: ...7 3 INPUT OUTPUT FUNCTION DESCRIPTION Table 9 Input Port Function Description Item Description 01 Not used Invalid 02 Breaking compulsorily When active this will force the breaker to transfer the ATS...

Страница 13: ...09 2 Abnormal volt It will output when 2 voltages is abnormal 10 Over current output It will output when loaded current exceeds the limit 11 Auto state output In will show output in automatic mode 12...

Страница 14: ...it can display the record information circularly including the temporal voltage of 1 and 2 detailed voltage current frequency and date and time Press and it will exit the current interface while pres...

Страница 15: ...ime Generator continuously run time can be set on the duration of maximum time for 99 hours 59 minutes 10 DATE AND TIME SETTING In the main screen press key and select 4 Date Time set and then press k...

Страница 16: ...0 2009 10 11 12 CONTROLLER INFORMATION In the main screen press key and select 6 Controller information and then press key the screen will show the controller information interface as follow Display c...

Страница 17: ...UPPLY The power of ATS is smartly controlled by controller As long as one power is normal it can ensures ATS voltage power supply normally and can be transferred properly Users should select power sup...

Страница 18: ...can also be applicable to dual power switching management for factories telecom industrial and civil buildings achieving remote control remote measuring remote communication functions More information...

Страница 19: ...gative DC negative input 20 B To start engine connect the terminal to battery positive DC positive input 8 35 V controller power supply 21 1 close input Detection of 1 switch closing state voltage fre...

Страница 20: ...HAT600N Series ATS Controller User Manual HAT600N Series ATS Controller Version 1 1 2019 09 05 Page 20 of 24 16 TYPICAL WIRING DIAGRAM Fig 3 ATYS3 Wiring Diagram Fig 4 SGQ N T Wiring Diagram...

Страница 21: ...HAT600N Series ATS Controller User Manual HAT600N Series ATS Controller Version 1 1 2019 09 05 Page 21 of 24 Fig 5 SGQ M Wiring Diagram Fig 6 VITZRO Wiring Diagram...

Страница 22: ...HAT600N Series ATS Controller User Manual HAT600N Series ATS Controller Version 1 1 2019 09 05 Page 22 of 24 Fig 7 Contactor Wiring Diagram Fig 8 ATYSM3S Wiring Diagram...

Страница 23: ...9 09 05 Page 23 of 24 Fig 9 Breaker Wiring Diagram Remark all above are application diagrams of HAT600N series ATS controllers However HAT600N and HAT600NB have no current sample input please skip ove...

Страница 24: ...ntroller with RS485 converter GND or PC GND It is recommended that a 120 resistor is added between A and B of RS485 Programmable output error Check programmable output connections and pay attention to...

Отзывы: