HAT600N Series ATS Controller User Manual 

HAT600N  Series  ATS  Controller                      Version  1.1                  2019-09-05                Page  10  of  24

 

7.  PARAMETERS CONFIGURATION   

7.1  PARAMETER SET DESCRIPTION   

In  the  main  interface,  press 

  key,  choose 

1.Parameters  setting

  and  then  press 

  key,  to  enter 

the password interface.   

Input  password  value  0-9  by 

  key,  and  shift  Right  by 

  key.  Press  the

  again  to  confirm  the 

password when four number is OK. If password is correct, it will enter into the parameter main interface. 

If it is wrong, it will directly exit and return to main interface. Factory Default Password is 1234. Press

 

to  shift  to  next  position  and  set  the  parameters.  Under  current  parameter  set  screen,  press 

  and 

enter  current  parameter  set  mode.  Current  value  of  the  first  line  screen  display  was  highlighted  with 

black. Press 

  key to change the value and press 

  key to shift position. Press 

  key again to 

confirm  the  settings.  If  the  value  number  is  within  the  setting  range,  the  value  will  be  saved  into  the 
internal memory of the controller; If it is beyond the range, then the parameter settings will not be saved. 

Long time pressing 

  will go back to the main display screen.   

7.2  PARAMETER CONFIGURATION TABLE 

Table 8 Parameter Configuration Item Table 

No. 

Item 

Range 

Default 

Description 

01  1# Normal Delay 

(0-9999)s 

10 

It is the delay of 1# power from voltage abnormal to 
voltage normal. 

02  1# Abnormal Delay 

(0-9999)s 

It  is  the  delay  of  1#  power  from  voltage  normal  to 
voltage abnormal. 

03  2# Normal Delay 

(0-9999)s 

10 

It is the delay of 2# power from voltage abnormal to 
voltage normal. 

04  2# Abnormal Delay 

(0-9999)s 

It  is  the  delay  of  2#  power  from  voltage  normal  to 
voltage abnormal. 

05  Close Breaker 

(0-20)s 

Closing  relay  output  pulse.  If  set  as  zero,  it  is 
continuous output. 

06  Open Breaker 

(1-20)s 

Opening relay output pulse. 

07  Transfer Interval 

(0-9999)s 

It  is  the  delay  from  1#  power  open  to  2#  power 
close or from 2# power open to 1# power close. 

08  Exceed Transfer   

(0-20.0)s 

0.0 

When  module  receives  a  closing  signal,  closing 
relay output. 

09  Again Close Time 

(0-20.0)s 

1.0 

When the breaker fail to close for the first time, the 
module will open breaker, and then attempt to close 
for the second time, if still failed to close the second 
time,  the  module  will  send  out  closing  breaker 
failure signal. 

10  Again Open Time 

(0-20.0)s 

1.0 

When the breaker fail to open for the first time, the 
module will close breaker, and then attempt to open 
for the second time, if still failed to close the second 
time,  the  module  will  send  out  opening  breaker 
failure signal. 

11  Start Delay 

(0-9999)s 

When  voltage  is  abnormal,  start  delay  begins  and 
starting signal is initiated. 
In  cycle  start,  starting  signal  is  initiated,  delay 
begins. After delay ends, if voltage abnormal, send 
fault  alarm  and  start  another  genset.  Start  delay 
should be higher than total starting time, minimum 
30 seconds. 

12  Stop Delay 

(0-9999)s 

It is the delay from #1 power is normal to send out 
stop generator signal. 

13  Cycle Run Time 

(1-1440)min  720 

Gens cycle start run time. 

14  Cycle Stop Time 

(1-1440)min  720 

Gens cycle stop time. 

Содержание HAT600N Series

Страница 1: ...HAT600N SERIES HAT600N HAT600NI HAT600NB HAT600NBI ATS CONTROLLER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD...

Страница 2: ...ing or storing in any medium by electronic means or other without the written permission of the copyright holder Applications for the copyright holder s written permission to reproduce any part of thi...

Страница 3: ...TION 5 4 OPERATING 6 5 LCD DISPLAY 7 6 COMMISSIONING 9 7 PARAMETERS CONFIGURATION 10 8 EVENT LOG 14 9 TIMING START 15 10 DATE AND TIME SETTING 15 11 LANGUAGE SETTING 15 12 CONTROLLER INFORMATION 16 13...

Страница 4: ...cy F2 4 Measure and display load active power apparent power power factor and 3 phase current 5 Over current alarm function 6 Over under voltage loss of phase reverse phase sequence over under frequen...

Страница 5: ...3P4W L L 80 625 V 80 480 V 3P3W L L 80 625 V Not used 1P2W L N 50 360 V 50 280 V 2P3W A B 80 625 V 80 480 V Rated Frequency 50 60Hz Close Open Trip Relay Output 16A AC250V Free Voltage relay output Pr...

Страница 6: ...off 1 or 2 power to off load 2 Close In Manual mode switch on 2 power to load Manual Press and controller enters into Manual mode Automatic Press and controller enters into AUTO mode Test Pressing thi...

Страница 7: ...Type Description 1 1 Gens Alarm Alarm When 1 genset occur failure this will display 2 1 Fail to Close Alarm When 1 breaker occur closing failure this will display 3 1 Fail to Open Alarm When 1 breake...

Страница 8: ...hase sequence is not A B C 10 2 Volt Normal Indication 2 source voltage is within the setting range Table 7 Display Status of Other Items upper to lower No Item Type Description 1 Trip alarm Alarm Tri...

Страница 9: ...s normal or not STOP TO TEST The start generator signal will turn off after pressing this key immediately CYCLE START When this mode is active generator start signal will cyclic output according to ma...

Страница 10: ...l to voltage abnormal 03 2 Normal Delay 0 9999 s 10 It is the delay of 2 power from voltage abnormal to voltage normal 04 2 Abnormal Delay 0 9999 s 5 It is the delay of 2 power from voltage normal to...

Страница 11: ...23 Under Frequency Return 0 0 75 0 Hz 48 0 Normal return value of over frequency 24 CT Ratio 5 65000 5 500 Current Transformer ratio 25 Rated Load Current 5 6000 A 500 Load rated current 26 Over Curre...

Страница 12: ...7 3 INPUT OUTPUT FUNCTION DESCRIPTION Table 9 Input Port Function Description Item Description 01 Not used Invalid 02 Breaking compulsorily When active this will force the breaker to transfer the ATS...

Страница 13: ...09 2 Abnormal volt It will output when 2 voltages is abnormal 10 Over current output It will output when loaded current exceeds the limit 11 Auto state output In will show output in automatic mode 12...

Страница 14: ...it can display the record information circularly including the temporal voltage of 1 and 2 detailed voltage current frequency and date and time Press and it will exit the current interface while pres...

Страница 15: ...ime Generator continuously run time can be set on the duration of maximum time for 99 hours 59 minutes 10 DATE AND TIME SETTING In the main screen press key and select 4 Date Time set and then press k...

Страница 16: ...0 2009 10 11 12 CONTROLLER INFORMATION In the main screen press key and select 6 Controller information and then press key the screen will show the controller information interface as follow Display c...

Страница 17: ...UPPLY The power of ATS is smartly controlled by controller As long as one power is normal it can ensures ATS voltage power supply normally and can be transferred properly Users should select power sup...

Страница 18: ...can also be applicable to dual power switching management for factories telecom industrial and civil buildings achieving remote control remote measuring remote communication functions More information...

Страница 19: ...gative DC negative input 20 B To start engine connect the terminal to battery positive DC positive input 8 35 V controller power supply 21 1 close input Detection of 1 switch closing state voltage fre...

Страница 20: ...HAT600N Series ATS Controller User Manual HAT600N Series ATS Controller Version 1 1 2019 09 05 Page 20 of 24 16 TYPICAL WIRING DIAGRAM Fig 3 ATYS3 Wiring Diagram Fig 4 SGQ N T Wiring Diagram...

Страница 21: ...HAT600N Series ATS Controller User Manual HAT600N Series ATS Controller Version 1 1 2019 09 05 Page 21 of 24 Fig 5 SGQ M Wiring Diagram Fig 6 VITZRO Wiring Diagram...

Страница 22: ...HAT600N Series ATS Controller User Manual HAT600N Series ATS Controller Version 1 1 2019 09 05 Page 22 of 24 Fig 7 Contactor Wiring Diagram Fig 8 ATYSM3S Wiring Diagram...

Страница 23: ...9 09 05 Page 23 of 24 Fig 9 Breaker Wiring Diagram Remark all above are application diagrams of HAT600N series ATS controllers However HAT600N and HAT600NB have no current sample input please skip ove...

Страница 24: ...ntroller with RS485 converter GND or PC GND It is recommended that a 120 resistor is added between A and B of RS485 Programmable output error Check programmable output connections and pay attention to...

Отзывы: