HAT530P/HAT530PC Series ATS Controller User Manual Page 9 of 18
b)
After adjusting the delays, press
. When S1/S2 power indicator and automatic indicator are
illuminated simultaneously, the adjusted values has been saved. The controller will go back to normal
status automatically after all LEDs are flashing 5 times rapidly and controller will work according to the
set delay values.
NOTE
:
1# Normal Delay set value must be no less than 1# Abnormal Delay, otherwise, 1# Normal Delay set value will
be forced to set as 1# Abnormal Delay set value. S2 Normal Delay set value must be no less than S2 Abnormal Delay,
otherwise, S2 Normal Delay set value will be forced to set as S2 Abnormal Delay set value.
5.5
FACTORY RESET DELAY VALUE
Firstly, make controller enter parameter setting status and then conduct the setting.
a)
Press
and
at the same time, when S1/S2 power indicator and auto indicator are
illuminated simultaneously; release the two buttons, then the auto indicator and S1/S2 power indicators
are extinguished simultaneously which means the delay timer of the controller can be set.
b)
press
, when S1/S2 power indicator and automatic indicator are illuminated simultaneously,
then reset the factory default. The controller will to back to normal status automatically after all LEDs
are flashing 5 times rapidly and controller will work according to the set delay values.
NOTE
:
The factory settings are S1/S2 abnormal delay of 5s and genset shutdown delay of 90s.
5.6
AUTO TRANS. AUTO RESTORE SETTING
Firstly, make controller enter parameter setting status and then conduct the setting.
Set “Auto Trans. Auto Restore/Auto Trans. Non-Restore” Steps:
a) Press
and
at the same time, when S1/S2 power indicator and auto indicator are
illuminated simultaneously, release the two buttons, then the auto indicator and S2 power indicator is
extinguished, S1power indicator and S1 close indicator are illuminated, which means the auto trans.
auto restore of the controller can be set.
b) Press
can circularly set two states:
Auto trans. non-restore when S1 power indicator and S1close indicator are illuminated, S2 power
indicator and S2 close indicator are extinguished.
Auto trans. auto restore when S2 power indicator and S2 close indicator are illuminated, S1 power
indicator and S1 close indicator are extinguished.
c) After adjustment, press
. When S1/S2 power indicator and auto indicator are illuminated
simultaneously, it indicates that the set parameter value has been saved successfully; all indicators on
the panel flash 5 times rapidly and controller will work according to the set state of auto trans.
auto-restore/auto trans. non-restore.
NOTE
: Turn on the power supply of the controller, auto trans. auto-restore/auto trans. non-restore set by the controller
can be judged by the following two situations:
If S1 power indicator and S1close indicator flash rapidly three times at the same time, it is auto trans. non-restore.
If S2 power indicator and S2 close indicator flash quickly three times at the same time, it is auto trans. auto restore.