HAT530P/HAT530PC Series ATS Controller User Manual Page 13 of 18
Table 5 - Terminal Function Table
Terminal No.
Item
Description
Remark
1
TA
A1
1# AC 3P4W voltage
input
If it is single phase input, only
connect with A1, N1.
2
B1
3
C1
4
N1
5
TB
A2
2# AC 3P4W voltage
input
If it is single phase input, only
connect with A2, N2.
6
B2
7
C2
8
N2
9
TC
NO
ATS power supply N
Provide power supply for ATS.
10
NO
11
LO
ATS power supply L
12
NC
Null
13
COM.OUT
Common port of
close/open output
14
OPEN OUTPUT
Open output
Volts free N/C output, capacity is
AC250V10A
15
16
S1 CLOSE OUTPUT
1# close output
Volts free N/C output, capacity is
AC250V16A
17
S2 CLOSE OUTPUT
2# close output
Volts free N/C output, capacity is
AC250V16A
18
TD
GEN START
Genset start output
Volts free N/C output, capacity is
AC250V7A
19
20
COM.IN
Input common port
21
FORCE OPEN
Forced open input
When it is active, set ATS as
breaking position and connect with
COMM.IN.
22
COM.IN
Input common port
23
S1 CLOSE INPUT
1# close input
Detect 1# switch close status, the
auxiliary contact input.
24
COM.IN
Input common port
25
S2 CLOSE INPUT
2# close input
Detect 2# switch close status, the
auxiliary contact input.
26
TE
120Ω RESISTANCE
RS485
impedance
resistance
Users need to connect the terminal
with Terminal 27 A(+) according to
the on-site networking for accessing
to the 120Ω impedance resistance
built in the controller.
27
A(+)
RS485
communication Port
The interior has been connected to
the 120Ω impedance resistance.
28
B(-)
29
GND
Connect to RS485 communication
shielding wire.