HAT530N ATS CONTROLLER Page 9 of 19
If the 2# power indicator flashes 3 times rapidly, the #2 power is main use.
If 1# & 2# power indicators flash 3 times rapidly at the same time, they are mutual- backup.
Note 2: Each time the controller is power on, the AC line system of the controller can be judged by the following four
conditions.
If 1# close indicator is light on, it is 1P2W;
If 1# close indicator, manual status indicator and 2# indicator are all illuminated, it is 3P4W.
If 1# close indicator and manual status indicator are illuminated, it is 2P3W.
If 2# close indicator and manual status indicator are illuminated, it is 3P3W.
Note 3: Each time the controller is power on, the auto trans. auto restore/auto trans. non-restore status of the controller
can be judged by the following 2 conditions.
If 1# power indicator and 1# close indicator flash 3 times rapidly at the same time, it is auto trans. non-auto restore
status.
If 2# power indicator and 2# close indicator flash 3 times rapidly at the same time, it is auto trans. auto restore
status.
Note 4: When the remote adjustment is disabled, PC cannot write parameter configuration to host computer.
Note 5: The factory default value is 1# power and 2# power abnormal delay for 5s, the genset will stop delay for 90s.
Note 6: 1# power abnormal delay: adjust the potentiometer (on back panel) of “1# power normal delay”; 2# power
abnormal delay: adjust the potentiometer (on back panel) of “2# power normal delay”; the set value of 1# power normal
delay should greater than or equal to the set value of 1# power abnormal delay, otherwise 1# power normal delay value
will be forced set to the set value of 1# power abnormal delay; the set value of 2# power normal delay should greater
than or equal to the set value of 2# power abnormal delay, otherwise 2# power normal delay value will be forced set to
the set value of 2# power abnormal delay;
Note 7: When parameter is set to restore the factory default setting and delay adjustment, press
button and press
button again; when the indicator of setting item No. flashes, press
button to save the configuration.