HAT530N ATS CONTROLLER Page 10 of 19
6
PARAMETER CONFIGERATION
6.1
PARAMETERS TABLE
Table 5 – Parameters Setting Table
No.
Item
Range
Default
Description
01 1# Normal Delay
(0-60)s
Can be set
via
controller
potentiomet
er
It is the delay of #1 power from voltage
abnormal to voltage normal. Generally, it is
10s.
02 1# Abnormal Delay (0-60)s
5
It is the delay of #1 power from voltage
normal to voltage abnormal.
03 2# Normal Delay
(0-60)s
Can be set
via
controller
potentiomet
er
It is the delay of #2 power from voltage
abnormal to voltage normal. Generally, it is
10s.
04 2# Abnormal Delay (0-60)s
5
It is the delay of #1 power from voltage
normal to voltage abnormal.
05 Close Delay
(0-20)s
5
Closing relay output pulse. If set as zero, it is
continuous output.
06
Open Delay
(1-20)s
5
Open relay output pulse.
07
Transfer Interval
(0-60)s
1
It is the delay from 1# power open to 2#
power close or from 2# power open to 1#
power close.
08 Exceed Transfer
(0-20.0)s
0.0
It is the extra output delay of the close relay
after the closing signal has received.
09 Start Delay
(0-3600)s
1
When voltage is abnormal, start delay begins;
start signal is initiated after the delay has
expired.
10 Stop Delay
(0-3600)s
90
When starting, if the mains voltage is normal,
stop delay begins; stop signal is initiated after
the delay has expired.
11
AC System
(0-3)
0
0. 3-phase 4-wire
1. 2-phase 3-wire
2. Single phase
3. 3-phase 3-wire
12
Rated Volt
(100-240)V 230
AC system rated voltage.
13 Rated Frequency
(50.0-60.0)
Hz
50.0
To offer standards for detecting of
over/under frequency.
14 Over Volt Enable
(0-1)
1
0: Disable
;
1: Enable
15 Over Voltage
(100-120)% 115
Voltage upper limit; it is abnormal when the
voltage has exceed the set value.
16 Over Volt Return
(100-120)% 113
Voltage upper limit return value; it is normal