![Smartgen HAT530N Скачать руководство пользователя страница 14](http://html.mh-extra.com/html/smartgen/hat530n/hat530n_user-manual_1297484014.webp)
HAT530N ATS CONTROLLER Page 14 of 19
8.2
FUNCTION DESCRIPTION OF WIRING TERMINALS
Table 7 - Terminal Function Table
No.
Items
Description
Remark
1
Aux. Output 1
NO
Default: ATS Power A
Phase
Volt-free relay contact output;
Rated 16A.
2
COM
3
NC
4
Aux. Output 2
NC
Default: ATS Power N
Phase
Volt-free relay contact output;
Rated 16A.
5
COM
6
NO
7
1# Close Output
Volt-free relay contact output;
Normally Open Output; Rated 10A.
8
2# Close Output
Volt-free relay contact output;
Normally Open Output; Rated 10A.
9
Open Output
Volt-free relay contact output;
Normally Open Output; Rated 10A.
10
COM1
Output COM of close switch and
open switch
COM1
11
GEN Start
Volt-free relay contact output;
Normally Close Output; Rated 7A.
12
13
A1
1# AC 3-phase 4 wire voltage
input
For single phase, only connect A1,
N1.
14
B1
15
C1
16
N1
17
1# Close Input
Detection of 1# ATS closing
status; auxiliary contact input
Connect COM2 is active.
18
2# Close Input
Detection of 2# ATS closing
status; auxiliary contact input
Connect COM2 is active.
19
Force Open
When active, the ATS is in Neutral
Position.
Connect COM2 is active.
20
COM Port
Input COM
COM2
21
A2
2# AC 3-phase 4 wire voltage
input
For single phase, only connect A2,
N2.
22
B2
23
C2
24
N2
LINK
Communication
Port
Communicate with PC/Program
update
Содержание HAT530N
Страница 1: ...HAT530N ATS CONTROLLER USER MANUAL ...