HAT162 ATS Controller User Manual                                                                                              Page 5 of 21

 

3.

 

SPECIFICATION 

Table 2 Specification Parameters 

Items 

Contents 

Operating Voltage 

AC power A1N1/A2N2 supply. 
Rated AC240V (range: AC170V~277V) 

Power Consumption 

Under rated voltage, power consumption is not more than 3VA 

AC Voltage Input: 
3-phase 4-wire 
2-phase 3-wire 
Single phase 2-wire 
3-phase 3-wire 

 
AC170V – AC277V (ph-N)   
AC170V – AC277V (ph-N)   
AC170V – AC277V (ph-N)   
AC170V – AC277V (ph-ph) (special order required) 

AC Frequency 

50/60Hz 

1# Close Relay 

16A AC250V Volt free output (Normally open) 

2# Close Relay 

16A AC250V Volt free output (Normally open) 

Oil Engine Start Relay 

7A AC250V Volt free output (Normally close) 

Programmable Output Relay 

7A AC250V Volt free output (Normally open) 

Communication 

LINK interface, MODBUS-RTU Protocol 

Case Dimensions 

86.9mmx158mmx119.5mm 

Panel Cutout 

73.5mmx144mm 

Working Temperature 

(-25~+70)°C   

Working Humidity 

(20~93)%RH 

Storage Temperature 

(-25~+70)°C 

Protection Level 

IP65:  when  water-proof  gasket  installed  between  control  panel  and 
enclosure.   

Insulation Strength 

Apply AC2.2kV voltage between high voltage terminal and low voltage 
terminal; 
The leakage current is not more than 3mA within 1min. 

Weight 

0.6kg 

 
 
 
 
 
 
 
 

Содержание HAT162

Страница 1: ...HAT162 ATS CONTROLLER USER MANUAL ...

Страница 2: ...cluding photocopying or storing in any medium by electronic means or other without the written permission of the copyright holder Applications for the copyright holder s written permission to reproduce any part of this publication should be addressed to SmartGen Technology at the address above Any reference to trademarked product names used within this publication is owned by their respective comp...

Страница 3: ... 4 4 1 AUTO MANUAL MODE SWITCH 7 4 4 2 MANUAL OPERATION 7 4 4 3 AUTO OPERATION 8 4 4 4 MANUAL TEST 8 5 CLOSE FAULT ALARM 8 6 WIRE CONNECTION 9 7 DEFINITION AND RANGE OF PARAMETERS 10 8 PARAMETERS SETTING 13 8 1 PARAMETERS SETTING MODE 13 8 2 PARAMETERS SETTING 13 8 3 RESET TO DEFAULT 14 9 TYPICAL APPLICATION 15 10 OVERALL DIMENSION AND PANEL CUTOUT 19 10 1 CASE DIMENSION 19 10 2 CUTOUT DIMENSION 1...

Страница 4: ...2 Main auto transfer and restore and No Main Use auto transfer and non auto restore power supply methods Measuring and displaying 2 way voltage and frequency 1 2 Phase voltage Ua Ub Uc Phase voltage Ua Ub Uc Line voltage Uab Ubc Uca Line voltage Uab Ubc Uca Frequency Hz Frequency Hz With over under voltage over under frequency loss of phase and reverse phase sequence detection functions Breaker cl...

Страница 5: ...y 16A AC250V Volt free output Normally open 2 Close Relay 16A AC250V Volt free output Normally open Oil Engine Start Relay 7A AC250V Volt free output Normally close Programmable Output Relay 7A AC250V Volt free output Normally open Communication LINK interface MODBUS RTU Protocol Case Dimensions 86 9mmx158mmx119 5mm Panel Cutout 73 5mmx144mm Working Temperature 25 70 C Working Humidity 20 93 RH St...

Страница 6: ...rameter configuration mode by pressing for 8s 1 Close Increase 1 close in manual mode Adjust parameters in parameter configuration mode 2 Close Decrease 2 close in manual mode Adjust parameters in parameter configuration mode Test Confirm It is active in manual mode While genset start signal is active press it can deactivate the genset start signal While genset start signal is inactive press it ca...

Страница 7: ...troller in Auto mode Lamp off controller in Manual mode Genset Status Lamp illuminates genset start signal outputs Lamp flashes genset start signal not output 4 4 OPERATION 4 4 1 AUTO MANUAL MODE SWITCH When the controller is normally working if auto manual mode indicator is off it means controller is in manual mode it can switch into auto mode by pressing the indicator will be normally light then...

Страница 8: ...d close again If controller still cannot detect the 1 close signal it will be regarded as 1 close failure and the alarm indicator illuminates at the same time Meanwhile if 2 supply voltage is normal and doesn t occur close fault then 2 power will be closed Process of trigger 2 supply close fault alarm is as below When 2 supply voltage is normal controller will initiate a command of close 2 supply ...

Страница 9: ... A2 5 N1 1 AC 3 phase 4 wire input Single phase 2 wire connect with A1 and N1 B1 and C1 are not connected 2 phase 3 wire connect with A1 B1 and N1 C1 is not connected 3 phase 3 wire connect with A1 B1 and C1 N1 is not connected special order required 6 C1 7 B1 8 A1 9 1 Close Relay Volt free normally open contact output Rated capacity 16A 250VAC 10 11 2 Close Relay Volt free normally open contact o...

Страница 10: ...e Rated 10A 250V F2 Fuse Rated 10A 250V 7 DEFINITION AND RANGE OF PARAMETERS Table 6 Parameters Definition and Range Table 1 No Items Range Default Description 1 AC System 1 4 1 1 3 Phase 4 Wire 3P4W 2 Single Phase 2 Wire 1P2W 3 3 Phase 3 Wire 3P3W special order required 4 2 Phase 3 Wire 2P3W 2 S1 Normal Delay 1 7 2 1 1s 2 5s 3 10s 4 20s 5 30s 6 45s 7 User defined Default 5s 3 S2 Normal Delay 1 7 ...

Страница 11: ...d Default 5s 7 Again Open Delay 1 7 2 1 1s 2 3s 3 5s 4 8s 5 10s 6 15s 7 User defined Default 3s 8 Transfer Delay Expired 1 7 1 1 0 5s 2 1s 3 2s 4 3s 5 4s 6 5s 7 User defined Default 0 5s 9 Gen Start Delay 1 7 4 1 3s 2 8s 3 15s 4 30s 5 50s 6 70s 7 User defined Default 30s 10 Gen Stop Delay 1 7 6 1 3s 2 8s 3 15s 4 30s 5 50s 6 70s 7 User defined Default 90s 11 Set Priority 1 3 1 1 S1 Priority 2 S2 Pr...

Страница 12: ...ue 70 100 75 Threshold value 8 Under Volt Return Value 70 100 77 Return value 9 Over Frequency Warn 0 1 1 0 Disabled 1 Enabled 10 Over Freq Set Value 100 120 110 Threshold value 11 Over Freq Return Value 100 120 104 Return value 12 Under Freq Warn 0 1 1 0 Disabled 1 Enabled 13 Under Freq Set Value 80 100 90 Threshold value 14 Under Freq Return Value 80 100 96 Return value 15 Loss of Phase 0 1 1 0 ...

Страница 13: ...inated indicators mean setting items numbers currently item number is 1 indicators mean these parameter values currently parameter value is 1 Configurable parameter list please check Table 6 Parameters Definition and Range Table 1 of item 7 Specific settings are as below 1 Select setting number which needs to adjust by pressing and 2 Enter into setting status by pressing and indicator flashes 3 Af...

Страница 14: ...ison Parameter Serial No LED Indicate Value Parameter Value LED Indicate Value 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 9 10 11 8 3 RESET TO DEFAULT In parameter setting mode press and LEDs illuminated and LED flashes After pressing LED illuminates for 2s indicating that the factory value has been restored Meanwhile all LEDs flash for 3 times and return back to the normal mode NOTE If do not need to restore ...

Страница 15: ...HAT162 ATS Controller User Manual Page 15 of 21 9 TYPICAL APPLICATION Fig 4 SGQ N Wire Connection ...

Страница 16: ...HAT162 ATS Controller User Manual Page 16 of 21 Fig 5 SGQ T Wire Connection ...

Страница 17: ... the above drawings for wiring The actual wiring on site is subject to the ATS switch wiring instructions And the capacity of the fuse should be selected according to the actual power consumption at the site which cannot be based on the fuse capacity in the drawing Fig 7 2 Phase 3 Wire Connection ...

Страница 18: ...of 21 Fig 8 Single Phase 2 Wire Connection NOTE The above drawing shows the wiring method is the AC phase voltage of 220V If the AC phase voltage is 110V in actual use please contact our technical personnel to confirm the specific wiring method ...

Страница 19: ... CUTOUT 10 1 CASE DIMENSION Unit mm Fig 9 Overall Dimensions 10 2 CUTOUT DIMENSION The controller has three installation ways panel built in internal 35mm slideway and internal screw mounting Panel built in and internal screw mounting are as below Unit mm Fig 10 Cutout Dimensions ...

Страница 20: ...HAT162 ATS Controller User Manual Page 20 of 21 10 3 INSTALLATION Fig 11 Panel Built in Installation Fig 12 35mm Guide Rail Installation Fig 13 Screw Installation ...

Страница 21: ...ns and voltages of 1 and 2 power Check F1 or F2 fuse Controller displays normal but switch not activate Check ATS Check the connections between controller and ATS 1 or 2 power LED flashes Check whether AC voltage is normal or not Alarm LED flashes If switch close failure alarms please check switch auxiliary contact wiring _________________________________ ...

Отзывы: