BAC06S SOLAR BATTERY CHARGER USER MANUAL
BAC06S Solar Battery Charger Version 1.0 2017-07-20 Page 9 of 19
No.
Items
Default
Adjustable Range
Description
24V
12V
24V
12V
battery voltage falls
below the set value.
17
Under
Voltage
Delay
120s
(0~3600)s
“Under voltage” alarm
will be initiated if the
battery voltage falls
below the set value
and the delay timer
has expired.
18
Under
Voltage
Return Value
25.0V 12.5V
(16.0~32.0)V
(8.0~16.0)V
The transition voltage
from “under voltage”
transfer to “normal
voltage”.
19
Under
Voltage
Return Delay
10s
(0~3600)s
“Under voltage” alarm
will be removed if the
battery
voltage
exceeds the return
value and the delay
timer has expired.
20
Communication
Address
10
1~254
RS485
communication
address
21
Baud Rate
0
(0~2)
0
:
9600bps
;
1
:
19200bps
;
2
:
38400bps
;
one stop-bit, no parity
bit