background image

                           

BAC06S SOLAR BATTERY CHARGER USER MANUAL

 

BAC06S  Solar  Battery  Charger              Version  1.0              2017-07-20                        Page  8  of  19

 

5.  PARAMETER CONFIGURATION

 

Basic Parameter Settings,

 

No. 

Items 

Default 

Adjustable Range 

Description 

24V 

12V 

24V 

12V 

1  

Battery Type 

(0~2) 

0:12V

1:24V

2:Self-adaption 

2  

Charging Stage 

(2~3) 

2: Two Stage;     

3: Three Stage 

3  

Max. 

Rated 

Current 

10.0A 

Nonadjustable 

Maximum 

charging 

current 

4  

Rated Current 

100% 

(0~100)% 

Maximum 

charging 

current percentage 

5  

Absorption 

Charge Voltage 

28.2V  14.1V 

(20.0~32.0)V 

(10.0~16.0)V 

The  charging  voltage 
of “Constant Voltage” 

6  

Absorption 

Charge Time 

(0~1) 

0: Disable; 1: Enable 

7  

Absorption 

Charge 

Time 

Setting 

1.0h 

(0.1~100)h 

The  charging  time  of 
“Constant Voltage” 

8  

Absorption 

Charge  Complete 

Current 

(0~1) 

0: Disable; 1: Enable 

9  

Complete 

Current Setting 

0.5A 

(0.20~3.00)A 

The  transition  current 
from 

“Absorption 

Charge”  transfer  to 
“Float Charge”. 

10  

Float 

Charge 

Voltage 

27.6V  13.8V 

(20.0~32.0)V 

(10.0~16.0)V 

The  voltage  of  “Float 
Charge” 

11  

AUTO 

BOOST 

Voltage 

25.6V  12.8V 

(20.0~32.0)V 

(10.0~16.0)V 

When the charger is in 
“Float Mode”, it enters 
into  “Quick  Charge”  if 
the  battery  voltage 

has  fallen  below  the 

set value.

 

12  

Trickle Charge 

(0~1) 

0: Disable; 1: Enable 

13  

Trickle 

Charge 

Voltage 

22.0V  11.0V 

(20.0~32.0)V 

(10.0~16.0)V 

The voltage of “Trickle 
Charge” 

14  

Trickle 

Charge 

Current 

50% 

(0~100)% 

Maximum 

charging 

current percentage 

15  

Battery 

Under 

Voltage Warn 

(0~1) 

0: Disable; 1: Enable 

16  

Under 

Voltage 

Set Value 

23.0V  11.5V 

(16.0~32.0)V 

(8.0~16.0)V 

“Under  voltage”  alarm 
will  be  initiated  if  the 

Содержание BAC06S

Страница 1: ...BAC06S SOLAR BATTERY CHARGER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD ZHENGZHOU SMARTGEN TECHNOLOGY CO LTD ...

Страница 2: ...Max Input Voltage DC48V Max Input Power 160W 320W Efficiency 96 97 MPPT Efficiency 99 Output Max Output Voltage 16V 32V Factory Default Float Voltage 13 8V 27 6V Rated Charging Current 10A Max Load Current 10A Working Condition Working Temp 30 55 C Storage Temp 40 85 C Working Humidity 20 RH 93 RH no condensation Overall Structure Weight 0 57kg Dimension 143mm 96mm 55mm L W H ...

Страница 3: ... increase in the electricity quantity of the battery b The second stage is named as Absorption Charge after the first stage the battery voltage is rise to absorption charge value rapidly and the charger voltage will keep constant The battery terminal voltage will stabilize in the absorption charge value with the decreasing of charging current c The third stage is named as Float Charge After the ab...

Страница 4: ... Quick Charge When the battery terminal voltage is relatively high the charging current will rise to rated value Large current charging operation leads to an increase in the electricity quantity of the battery b The second stage is named as Float Charge The charging current will decrease with the rising of battery electricity As soon as charging current value falls below 0 3A the battery is basica...

Страница 5: ...h The charging time of Constant Voltage 8 Absorption Charge Complete Current 1 0 1 0 Disable 1 Enable 9 Complete Current Setting 0 5A 0 20 3 00 A The transition current from Absorption Charge transfer to Float Charge 10 Float Charge Voltage 27 6V 13 8V 20 0 32 0 V 10 0 16 0 V The voltage of Float Charge 11 AUTO BOOST Voltage 25 6V 12 8V 20 0 32 0 V 10 0 16 0 V When the charger is in Float Mode it ...

Страница 6: ...y voltage falls below the set value and the delay timer has expired 18 Under Voltage Return Value 25 0V 12 5V 16 0 32 0 V 8 0 16 0 V The transition voltage from under voltage transfer to normal voltage 19 Under Voltage Return Delay 10s 0 3600 s Under voltage alarm will be removed if the battery voltage exceeds the return value and the delay timer has expired 20 Communication Address 10 1 254 RS485...

Страница 7: ...s up if solar cell panel correctly connect and solar voltage exceeds 6V If load over current battery indicator and solar indicator flash per 0 5s Battery Indicator Indicator lights up if battery correctly connect to the battery and battery voltage exceeds 3V If fail to charge battery indicator flashes per 0 5s If load over current battery indicator and solar indicator flash per 0 5s NOTE 1 During ...

Страница 8: ...rovide lighting in the dark and also available for other functional load Display Connecting monitoring device to portA and portB of RS485 to display the charging status data Mains Charger Mains charger can be backup power supply for the battery if battery volt is too low caused by the solar cells fault heavy load and long term un sufficient energy It is avoiding the battery to over discharge Inter...

Страница 9: ...BAC06S SOLAR BATTERY CHARGER USER MANUAL BAC06S Solar Battery Charger Version 1 0 2017 07 20 Page 18 of 19 10 CASE DIMENSIONS Unit mm BAC06S Mounting Dimensions ...