Longo programmable controller LPC-2.DT1B
Actual temp.:
Actual room temperature 0 .. 5000 represents 0.00 .. 50.00 °C.
Actual light:
Actual room light intensity 0 .. 100 represents 0 .. 100%.
Light x (Off/On) command:
remote On/Off command for individual light. This command is enabled
using corresponding Light x (Local/Remote) command.
Light x (Local/Remote) command:
Enables corresponding light On/Off remote command.
Clock display enable command:
Time Clock display enable command from MCU. When active, time
will be displayed on CP.
Light Off MIN set value:
Below this set value, LCD back light will turn off. Value 0 .. 100
represents 0 .. 100 % light intensity.
Clock set value
:
Clock to be displayed on LCD in HH:MM format. High byte of an unsigned integer
variable represents hours (HH) and low byte represents minutes (MM). For example value
2592 ( [10*256]+32 = 2592) will be represented as 10:32.
Communication:
Used for communication diagnose between MCU and CP. Normally this bit is
toggled every 1 second from MCU side and than Communication feed back status is
supervised on the MCU side.