background image

Longo programmable controller LPC-2.DP1

measured by the panel is inside temperature dead band values (default dead band is 0.5 °C).        

Error 

       

In case of CP internal on communication fault, “ERR” sign appear on LCD.

Set

  

When any of four buttons is pressed more than certain time, “SET” sign appear on LCD and buttons 
functioning is enabled. After “SET” sign is off, push buttons functions are disabled.

3.2 Functions 

PI controller

Output variable range is 0 to 10000 (0..100%) in heating and/or cooling mode respectively . 

Values are used for analog/digital (0..100% / I.,II.,III. speed ) output reference for the fan speed 
and/or the output for the heat/cool actuator (0..100% / On-Off valve).
The dynamics of PI calculation is defined by P& I parameters.

Example: 

If proportional – P parameter (default = 25) is set to 1 and difference between measured 
temperature and temperature set point is changed to +1 °C, the PI output value will change from 
example 5000 to 5100. On the other hand if the difference is changed to -1 °C, PI output value will 
change from example 5000 to 4900.
If integral – I parameter (default = 5) is set to 1 and difference between measured temperature and 
temperature set point is +1 °C, the PI output value will increase every second by 1. On the other 
hand if the difference is -1 °C, the PI output value will decrease every second by 1.

2/4 pipe system selection

While 4-pipe (factory default) system active, controller will activate hot water actuator when 
heating is required and cool water actuator when cooling is required. 
In case 2-pipe system is active, hot water actuator will be operated regardless whether heating or 
cooling is needed. Mode of operation (closing, opening) is dependent on 

Winter/Summer

 parameter.

Example:
System selected is 2-pipe , summer mode active and SP is lower than room temperature. CP will 
start cooling with activating heat valve. In 2-pipe system cool valve is always inactive.

Frost protection

Function activates heat command when room temperature measured by the panel drops below 7 °C.
This function has priority over all control panel integrated functions.

Window open

Panel will operate in special mode if opened window and opened balcony door are detected. This 
function is enabled by enabling parameters 

Balcony door  En. 

or

  Window En.

 When this function is 

active and one of parameters 

Window

 or 

Balcony Door

 commands is active, fan will stop and valves 

for heating and cooling will close (delay of 1 minute is add with Balcony door command).

4

Содержание LPC-2.DP1

Страница 1: ...USER MANUAL Longo programmable controller LPC 2 DP1 Temperature Control panel Version 4 SMARTEH d o o Poljubinj 114 5220 Tolmin Slovenia Tel 386 0 5 388 44 00 e mail info smarteh si www smarteh si...

Страница 2: ...Longo programmable controller LPC 2 DP1 Written by SMARTEH d o o Copyright 2016 SMARTEH d o o User Manual Document Version 4 March 2016 i...

Страница 3: ...ot include damage due to transport or because of unconsidered corresponding regulations of the country where the module is installed This device must be connected properly by the provided connection s...

Страница 4: ...1 2 FEATURES 2 3 OPERATION 3 3 1 Operational modes 3 3 2 Functions 4 3 3 Parameters 5 4 INSTALLATION 7 4 1 Connection scheme 7 4 2 Mounting frame selection 9 4 3 Mounting instructions 10 4 4 Module l...

Страница 5: ...eed I speed II speed III AUTO or OFF modes of operation can be selected Fan mode is represented with left blue LCD bar graph With ECO economy OFF and ERR error signs on LCD CP status is represented Co...

Страница 6: ...controller off 10 position LCD bar graph for temperature set point 4 position LCD bar graph for manual fan speed auto and controller off Light intensity measurement LCD intensity control Step less or...

Страница 7: ...led Display will return to stand by mode if touch buttons are not pressed for a while 5 seconds Changing operation modes Request for switching between CP normal and economic operating mode is done wit...

Страница 8: ...re and temperature set point is 1 C the PI output value will increase every second by 1 On the other hand if the difference is 1 C the PI output value will decrease every second by 1 2 4 pipe system s...

Страница 9: ...sed Winter Summer Used only for two pipe system to change calculation for Hot valve and Fan speed Winter heating 0 to Summer cooling 1 4 2 pipe Four pipe system manages hot and cold water pipes simult...

Страница 10: ...into PI calculation algorithm as SP Fan mode set Fan mode on CP panel can be remotely changed by main module 0 1 2 3 4 Off I II III auto The change is made by setting the Fan Remote Cmd command bit Re...

Страница 11: ...Longo programmable controller LPC 2 DP1 4 INSTALLATION 4 1 Connection scheme Figure 2 Connection scheme 7...

Страница 12: ...cted II middle speed selected III maximum speed selected AUTO auto speed selection OFF module functions switched off TB1 Up left Fan mode Increase Mode speed selection TB2 Down left Fan mode Decrease...

Страница 13: ...were not verified by Smarteh Before installation verify compatibility of non listed frames Module housing has a fin on each side which can be easily removed with knife cutter or pliers This adaptation...

Страница 14: ...connected to the main power supply Module should be positioned in the wall inside of the room Avoid direct sunlight or positioning near heating cooling source object Usage of cover frames and holders...

Страница 15: ...DP1 with cover plate LPC 2 DP1 is connected to the main module with interconnection cable e g SSK ICM 7 which must be ordered together with LPC 2 DP1 module When more modules e g LPC 2 CR1 LPC 2 CH1...

Страница 16: ...ounting module 01 derivation code 001 version code reserved for future HW and or SW firmware upgrades D C 01 10 is the date code 01 week and 10 year of production Label 2 description S N DP1 S9 090000...

Страница 17: ...Longo programmable controller LPC 2 DP1 5 REGULATION DIAGRAM 13...

Страница 18: ...main module Interconnection connector type RJ 12 6 6 Power consumption 1 W Dimensions W x H x D 75 x 49 x 29 mm Weight 50 g Maximum altitude 2000 m Mounting position horizontal Ambient temperature 0 t...

Страница 19: ...scribes all the changes to the document Date V Description 30 03 16 4 Added sentence about sealing junction box and pipes on page 10 01 07 12 3 CGP General update 20 07 10 2 Updated regulation diagram...

Страница 20: ...Longo programmable controller LPC 2 DP1 8 NOTES 16...

Отзывы: